The direct answer: A 3 wire stop start wiring diagram controls a motor contactor using a normally closed (NC) Stop pushbutton in series with a normally open (NO) Start pushbutton, which is paralleled by the contactor’s NO auxiliary seal-in contact. The term '3-wire' refers specifically to the three control conductors running to the remote pushbutton station (Line in, Start/Seal-in parallel node, and Coil return), excluding the equipment grounding conductor. This guide assumes a standard 120VAC control circuit derived from a 480V/120V step-down control transformer, utilizing 14 AWG THHN copper wire protected by a 5A Class CC fuse.
Physical Terminal Mapping & Component Specs
Before tracing the path, you must identify the physical terminals on the bench. Misidentifying an auxiliary contact block as a power pole is a common failure point that results in immediate control circuit failure. Below is the exact pin mapping for a standard 9A IEC-style motor starter assembly.
| Component | Example Part (IEC) | Terminal IDs | Function in Circuit | 120VAC Wire Color |
|---|---|---|---|---|
| Control Transformer Secondary | Hammond 185F120 | X2 (Hot), X1 (Neutral) | Provides isolated 120VAC control power | Red (X2), White (X1) |
| Overload Relay (NC Contact) | Eaton PKZM0-10 | 95 (In), 96 (Out) | Breaks control circuit on thermal trip | Red |
| Stop Pushbutton (NC) | Siemens 3SU1150-0AB40-1AA0 | 11 (In), 12 (Out) | Momentary break to drop the coil | Red |
| Start Pushbutton (NO) | Siemens 3SU1150-0AB30-1AA0 | 13 (In), 14 (Out) | Momentary make to energize coil | Red (In), Black (Out) |
| Contactor Auxiliary (NO) | Eaton XTCE009B01 (Aux: DILM10) | 13 (In), 14 (Out) | Seal-in / Holding contact | Red (In), Black (Out) |
| Contactor Coil | Eaton XTCE009B01 | A1 (+/Hot), A2 (-/Neutral) | Electromagnet that pulls power poles | Black (A1), White (A2) |
Node-by-Node Circuit Trace (Source to Load)
To understand how the 3 wire stop start wiring diagram functions, we must trace the current path from the control power source, through the logic nodes, to the coil, and back. This trace assumes the main disconnect is ON and the control transformer is energized.
- Source Origin: Current leaves the X2 terminal of the control transformer (120VAC Hot) through a 5A fuse, traveling via a Red 14 AWG wire to terminal 95 of the Overload Relay.
- Overload Logic: Current passes through the internal NC contact of the overload relay, exiting at terminal 96. (If the motor previously drew excessive current and tripped the bimetallic strip, this path is open, and the circuit stops here).
- Stop Button Entry: The Red wire from terminal 96 lands on terminal 11 of the Stop pushbutton. Current passes through the NC contacts, exiting at terminal 12. This creates our primary logic node, Node A.
- The Parallel Split (Node A): At Node A, the circuit splits into two parallel paths.
- Path 1 (Manual Start): A wire jumps from Node A to terminal 13 of the Start pushbutton.
- Path 2 (Seal-In): A simultaneous wire jumps from Node A to terminal 13 of the contactor’s auxiliary NO contact block.
- Logic Convergence (Node B):
- When the Start button is pressed, current flows from 13 to 14.
- Simultaneously, once the contactor pulls in, the auxiliary contact closes, allowing current from 13 to 14.
- Both terminal 14s are jumpered together to form Node B.
- Coil Energization: A Black wire carries current from Node B directly to the A1 terminal of the contactor coil. The electromagnetic field collapses the air gap, pulling in the main power poles and the auxiliary seal-in contact.
- Return Path: Current exits the coil at terminal A2 via a White (Neutral) wire, returning directly to the X1 terminal of the control transformer, completing the 120VAC circuit.
Decoding the Diagram Symbols
When reading the schematic for a 3 wire stop start wiring diagram, the symbols dictate the physical state of the contacts when the system is de-energized (the 'shelf state').
- Normally Open (NO) Symbol: Represented by a gap between two diagonal lines or a simple break. For the Start button (13-14) and Aux contact (13-14), this means no current flows until mechanical force (a finger or the electromagnet) closes the gap.
- Normally Closed (NC) Symbol: Represented by a continuous line interrupted by a diagonal slash or a 'bubble'. For the Stop button (11-12) and Overload (95-96), current flows freely in the shelf state. Pressing the Stop button physically lifts the contact, breaking the path.
- Coil Symbol: A circle or rectangle with 'A1' and 'A2' inside. In NEMA schematics, this may be labeled 'M' (for Motor starter), while IEC schematics strictly use the alphanumeric terminal designations (A1/A2).
- Thermal Overload Element vs. Contact: The schematic will show a heater element (usually a box with a line through it) in the main power lines (L1, L2, L3), mechanically linked via a dashed line to the NC contact (95-96) in the control circuit. This dashed line indicates that a thermal event in the power circuit physically actuates the control circuit switch.
Multimeter Verification & Troubleshooting
Never guess if a connection is solid. Use a digital multimeter (like a Fluke 117 or 87V) to verify the 3 wire stop start wiring diagram logic. Always perform continuity checks with the circuit de-energized and LOTO applied.
Step-by-Step Continuity Verification
- Verify the Stop Circuit: Set your meter to Continuity (audio beep). Place probes on terminal 96 of the Overload and terminal 12 of the Stop button. You should read < 1 ohm. If OL (Open Line), the overload is tripped or the wire is broken.
- Verify the Start Button: Place probes on terminal 13 and 14 of the Start pushbutton. With the button released, the meter must read OL. Press and hold the button; the meter should drop to < 1 ohm.
- Verify the Seal-In Contact: Place probes on terminals 13 and 14 of the auxiliary block. It should read OL. Manually push the contactor's armature in with a flathead screwdriver (or your finger if safe/de-energized). The meter must read < 1 ohm.
- Verify the Coil: Place probes across A1 and A2. A healthy 120VAC contactor coil (like the Eaton XTCE) will typically read between 15 to 45 ohms depending on the exact frame size. If it reads OL, the coil is burnt open. If it reads 0.1 ohms, the coil is shorted.
Live Voltage Troubleshooting Matrix
If the motor fails to start during live operation, use the following decision matrix. Set your meter to AC Voltage, referencing all measurements to the X1 (Neutral) terminal of the transformer.
| Symptom | Meter Probe Location | Expected Reading | Diagnostic Conclusion & Fix |
|---|---|---|---|
| Motor won't start, no click | Stop PB Terminal 11 to X1 | 120VAC | If 0V: Blown control fuse or open transformer secondary. |
| Motor won't start, no click | Stop PB Terminal 12 to X1 | 120VAC | If 0V: Overload tripped (reset OL) or Stop PB NC contact failed. |
| Motor starts but stops when Start PB is released | Aux Contact Terminal 14 to X1 (while holding Start PB) | 120VAC | If 120V is present but drops on release: Aux seal-in contact (13-14) is dirty, misaligned, or failed to close. Clean or replace aux block. |
| Contactor hums loudly and chatter | Coil A1 to A2 (AC Voltage) | 114V - 126V | If voltage is < 102V (85% of nominal): Coil brownout. Check for undersized control transformer or excessive voltage drop on long 14 AWG control runs. |
For deeper diagnostic procedures on motor control circuits, refer to the Fluke motor troubleshooting guidelines, which detail the specific safety categories and voltage drop thresholds for industrial contactors. Additionally, the foundational logic of these seal-in circuits is extensively documented in All About Circuits' motor control chapter, which provides excellent baseline schematics for both 2-wire and 3-wire pilot devices.
By strictly following the terminal mapping, verifying the node-by-node trace with your meter, and understanding the physical state of the diagram symbols, you can build, commission, and troubleshoot a 3-wire motor starter with absolute certainty.






