If your panel’s factory bus is out of terminal holes, you need an add-on ground bar in breaker box enclosures to terminate new equipment grounding conductors (EGCs). The direct answer for sizing and selection is simple: you must buy an add-on bar that exactly matches your panel’s manufacturer brand, is rated for the wire gauges you are terminating (typically #14 to #1/0 AWG), and mounts using the panel’s pre-punched knockout holes. For a standard 200-Amp residential panel, this usually means picking up a $15 to $20 OEM accessory bar like the Square D PK7GTA or Siemens GBK4.
But before you start stripping wires, you need to understand the physics of fault current. Installing a ground bar incorrectly—or confusing it with a neutral bar—turns a life-saving safety system into a lethal hazard.
The Hazard: What Happens When Fault Current Has Nowhere to Go
The equipment grounding conductor (the bare copper or green wire) has one job: to provide a low-impedance path back to the source so the breaker trips instantly during a short circuit.
Imagine a hot (black) wire inside your metal-cased washing machine chafes against the chassis. Without a properly terminated ground bar and continuous EGC, the metal case becomes energized at 120V. The breaker does not trip because there is no return path for the current. The moment you touch the washer and a grounded surface (like a wet floor or a metal sink), you become the return path. This results in severe shock or electrocution.
When your ground bar is correctly installed and torqued, the fault current rushes back through the EGC to the panel, hits the main bond, and travels back to the transformer. This massive surge of current (often hundreds of amps) trips the breaker in milliseconds, clearing the fault before it can cause a fire or injury.
Ground vs. Neutral vs. Bond: The Physics of the Panel
To wire a ground bar correctly, you must understand the distinct roles of the three conductors sharing your panel. Confusing them is the most common cause of failed electrical inspections and dangerous subpanel installations.
- Neutral (Grounded Conductor): The white wire. It carries the normal, continuous return current back to the source during everyday operation. It is a current-carrying conductor.
- Ground (Equipment Grounding Conductor / EGC): The bare or green wire. It carries current only during a fault. It connects to all non-current-carrying metal parts (appliance cases, metal boxes, panel enclosures).
- Bond (Main Bonding Jumper): The physical connection (usually a green screw or a metal strap) that ties the neutral bar and the ground bar together.
The Golden Rule: The bond between neutral and ground must exist only at the main disconnect (the first means of disconnect, usually your main outdoor or indoor panel). In any downstream subpanel, the neutral bar and ground bar must be physically isolated. If you bond a subpanel, normal return current will travel back on both the neutral wire and the bare ground wires, energizing your plumbing and appliance chassis under normal conditions.
Sizing and Selecting the Right Ground Bar (Decision Tree)
You cannot mix and match ground bar brands. A Square D bar will not align with the mounting holes in a Siemens panel, and forcing it with self-tapping screws voids the UL listing and compromises the fault-current path. Use the decision matrix below to select your exact part.
| Panel Brand / Type | Required Part Number | Wire Capacity | Avg. Price | Decision Rule |
|---|---|---|---|---|
| Square D (Homeline) | PK7GTA | #14 to 1/0 AWG (Cu/Al) | $14 - $18 | Choose if breakers say "HOM". |
| Square D (QO) | PK4GTA | #14 to #2 AWG (Cu/Al) | $16 - $22 | Choose if breakers have a red indicator window. |
| Siemens | GBK4 | #14 to 1/0 AWG (Cu/Al) | $12 - $16 | Choose if panel label says Siemens or Murray. |
| Eaton (BR Type) | BRPGK | #14 to #2 AWG (Cu/Al) | $15 - $20 | Choose if breakers are 1-inch wide, black handles. |
| Eaton (CH Type) | CHPGK | #14 to #2 AWG (Cu/Al) | $18 - $24 | Choose if breakers are 3/4-inch wide, tan handles. |
Step-by-Step: Installing an Add-On Ground Bar
Adding a ground bar in a main panel involves working inches away from the unfused, always-live service entrance lugs. While you are only terminating ground wires (which carry no current under normal conditions), a slipped screwdriver can be fatal.
Prerequisite: Shut off the main breaker to de-energize the branch circuit busbars. If you must work near the main lugs, wear arc-flash rated PPE or hire a professional.
- Verify Dead: Use a non-contact voltage tester (NCVT) and a CAT III or CAT IV multimeter to verify the branch busbars are de-energized. Test a known live source first to prove your meter works.
- Locate Mounting Holes: Look at the back wall of the panel enclosure. Manufacturers pre-punch threaded or unthreaded holes specifically for add-on ground bars. Do not drill your own holes; you risk hitting wires behind the backplane or compromising the enclosure's structural integrity.
- Remove the Knockout: Use a flathead screwdriver and a hammer to gently tap out the metal knockout covering the mounting holes. Remove any sharp burrs with a file to prevent wire insulation damage.
- Mount the Bar: Secure the new ground bar using the machine screws provided in the kit. Torque them tightly to the enclosure backplane to ensure a solid metal-to-metal bond. The panel enclosure itself is part of the ground path.
- Route and Terminate EGCs: Route your bare or green equipment grounding conductors to the new bar. Strip insulation (if using green THHN) to the exact length required by the bar's wire guide.
- Torque to Spec: Tighten the terminal screws. NEC 110.14(D) requires terminals to be tightened to the manufacturer's specified torque. For most #12 to #2 AWG ground bars, this is between 20 and 35 inch-pounds. Use a calibrated torque screwdriver (like the CDI 401SM or Wiha 64501).
Verification: Testing the Grounding Path
Once installed, you must verify the ground bar is properly bonded to the panel and the rest of the system. A loose mounting screw or a missed main bonding jumper will render your new bar useless during a fault.
1. Continuity Test (Multimeter):
With the main breaker still OFF, set your multimeter to the lowest resistance (Ohms) setting. Place one probe on the newly installed ground bar and the other on the main neutral busbar. You should read less than 1.0 ohm (ideally 0.2 to 0.5 ohms). If you read OL (open loop) or high resistance, your main bonding jumper is missing, loose, or the new bar is not making solid contact with the enclosure.
2. Fault Loop Impedance Test (Advanced):
For a true measure of safety, professionals use a low-impedance loop tester (such as the Fluke 1621 or Kyoritsu 4140) at the furthest receptacle on the circuit. This tool sends a brief, high-current pulse between hot and ground to measure the total impedance of the fault path. While the NEC does not specify a hard ohm limit for EGC loop impedance, a reading under 1.0 ohm ensures more than enough fault current to trip a standard 15A or 20A breaker in under 100 milliseconds.
When to Call a Licensed Electrician
While terminating ground wires to a newly mounted bar is a straightforward mechanical task, the broader grounding and bonding system is heavily regulated. Mike Holt Enterprises and the NFPA consistently emphasize that improper bonding is a leading cause of electrical fires and shocks.
You must defer to a licensed electrician and your local Authority Having Jurisdiction (AHJ) if:
- The Main Bonding Jumper is Missing: If your continuity test fails and you cannot locate the green bonding screw or bonding strap in the main panel, do not attempt to fabricate one. This requires precise sizing based on the service entrance conductors (per NEC Table 250.102(C)(1)).
- Grounding Electrode Conductor (GEC) Issues: The thick bare wire that runs from your panel to the ground rods or Ufer ground is the GEC, not an EGC. If this wire is corroded, undersized, or disconnected, it requires a professional to remediate and re-test earth ground resistance.
- Subpanel Conversions: If you are converting an old panel where grounds and neutrals are illegally mixed on the same bar in a subpanel, an electrician must isolate the neutral bar (by removing the bond and pulling the neutrals off the ground bar) to prevent objectionable neutral current from energizing your home's grounding system.
- Service Entrance Upgrades: Any work involving the meter base, the service drop from the utility, or upgrading the main service disconnect requires utility coordination and a licensed professional.
Always treat local electrical codes as the minimum safety standard. Your local inspector has the final authority on whether your specific panel configuration and grounding methods meet the requirements for your jurisdiction.






