A double pole single throw (DPST) switch diagram illustrates a component that simultaneously makes or breaks two independent electrical circuits using a single actuator. In modern DIY automation, HVAC control, and panel building, this "switch" is almost exclusively an electromechanical relay or a 2-pole contactor. The diagram is split into two galvanically isolated halves: a low-power coil circuit that acts as the brain, and a high-power contact circuit that acts as the muscle.
The Core Anatomy: Coil vs. Contact Side Wiring
Reading a DPST relay diagram requires you to mentally separate the control side from the load side. They share a mechanical linkage (the armature) but have no direct electrical connection.
- The Coil Side (Control): Typically labeled
A1andA2(or 13/14 on some IEC contactors). This is the electromagnet. When you apply the rated voltage here, it generates a magnetic field that pulls the armature down. - The Contact Side (Load): For a DPST-Normally Open (NO) configuration, the terminals are usually numbered
13-14(Pole 1) and23-24(Pole 2). When the coil energizes, 13 connects to 14, and 23 connects to 24 simultaneously.
Rating Table: Which Column Governs Your Load?
The most common mistake when reading a DPST switch diagram is sizing the component based on the maximum printed amperage. A relay rated for "25A" might only handle 25A for a resistive heater, but will weld its contacts shut if used on a 25A motor. You must look at the utilization category.
| Parameter | Resistive (AC-1) | Inductive (AC-15) | Motor (AC-3) |
|---|---|---|---|
| Typical Loads | Heaters, incandescent bulbs | Solenoids, transformers, contactor coils | Compressors, pumps, fans |
| Nominal Current (Ie) | 25A | 10A | 7.5A (approx. 2 HP at 240V) |
| Breaking Capacity | 1x Nominal | 10x Nominal (inductive kick) | 8x to 10x FLA (Locked Rotor Amps) |
| Inrush Tolerance | Low (steady state) | Moderate | Extreme (lasts 2-5 seconds) |
Which Rating Column Governs This Load?
The governing column is strictly dictated by the worst-case transient state of your specific load, not its steady-state running current.
- If Resistive: The AC-1 column governs. Steady-state current equals inrush current.
- If Inductive: The AC-15 column governs. When breaking the circuit, the collapsing magnetic field creates a massive voltage spike. You must derate the resistive rating by at least 60%.
- If Motor: The AC-3 column governs. Motors draw 600% to 800% of their Full Load Amps (FLA) during startup. A 10A motor requires a contactor rated for at least 60A-80A breaking capacity.
Step-by-Step: Wiring the Double Pole Single Throw Switch Diagram
- Wire the Coil Circuit (A1/A2): Connect your control voltage. If you are driving a DC coil (e.g., 24VDC) from a transistor, PLC, or microcontroller, you must wire a flyback diode (like a 1N4007) in reverse bias across A1 and A2. When the coil de-energizes, it generates a high-voltage inductive kickback that will instantly destroy solid-state driving components without this diode.
- Wire Pole 1 (13/14): Connect your Line 1 (L1) to terminal 13, and your Load 1 (T1) to terminal 14.
- Wire Pole 2 (23/24): Connect Line 2 (L2) to terminal 23, and Load 2 (T2) to terminal 24. For 240V split-phase loads, both poles carry hot legs. For 120V control circuits, use Pole 1 for the hot leg and Pole 2 for the neutral (though switching neutrals is generally discouraged unless it's a fully isolated appliance).
- Torque the Terminals: Use a torque screwdriver. For standard M3.5 relay screws, torque to 1.0 - 1.2 Nm. Under-torquing causes high resistance and melted terminal blocks; over-torquing strips the brass threads.
Testing Dead and Live: Multimeter Thresholds
Do not rely on visual inspection. Carbon tracking and pitted contacts look perfectly fine to the naked eye until they fail under load.
Dead Testing (Power Off)
- Coil Resistance: Set your meter to Ohms (Ω). Measure across A1 and A2. A healthy 24VDC coil typically reads between 300Ω and 600Ω. A 120VAC coil will read much higher (2kΩ - 10kΩ). If it reads OL (open), the internal coil wire is snapped. If it reads 0.5Ω, it is shorted.
- Contact Continuity: Set meter to continuity. Measure 13 to 14. It should read OL. Manually press the armature down with a non-conductive tool; it should drop to < 0.5Ω. Repeat for 23 to 24.
Live Testing (Power On, Under Load)
- Coil Voltage: Measure AC or DC voltage across A1 and A2 while energized. It must be within ±10% of the nominal rating. A 24V coil receiving 19V will chatter and overheat.
- Contact Voltage Drop (The Ultimate Test): With the relay energized and the load running, set your multimeter to millivolts (mV). Place one probe on 13 and the other on 14. A healthy contact pair will drop less than 20mV. If you read > 50mV, the contacts are pitted or carbonized and the relay must be replaced. A high voltage drop means the contacts are generating excess heat (P = I²R).
Repair vs. Replace: The Final Decision Path
Electromechanical components are consumables. The contacts physically degrade every time they break an inductive or motor load due to arc erosion. Use this decision matrix to determine your next step.
| Symptom / Test Result | Diagnosis | Action |
|---|---|---|
| Coil reads OL (Open) | Internal coil winding burned out. | Replace. Cannot be repaired. |
| Contacts read > 50mV drop under load | Severe pitting / carbon buildup. | Replace. Do not file or sand contacts; this removes the silver-alloy plating. |
| Relay chatters loudly when energized | Shading ring broken or coil voltage >10% low. | Replace if shading ring is broken; Fix power supply if voltage is low. |
| Contacts welded shut (fails to drop out) | Exceeded AC-3 breaking capacity. | Replace and upsize to a higher AC-3 rated contactor. |
The Final Selection Decision Path
Stop guessing which component to buy. Follow this exact path to select your DPST switch:
- IF your load is purely resistive (heaters, lighting) AND under 20A THEN select a standard general-purpose relay.
- IF your load is a motor/compressor AND under 3 HP (240V) THEN select a definite-purpose contactor.
- IF your control signal is 24VDC from a PLC, thermostat, or microcontroller THEN ensure the coil is rated for 24VDC, not 24VAC.
The Default Concrete Pick: For 90% of DIY automation, HVAC control panels, and maker projects requiring a DPST configuration, buy the Omron G7L-2A-BUB. It features a 24VDC coil, DPST-NO contacts, and is rated for 25A resistive (AC-1) and handles standard fractional HP motors reliably. It mounts via standard 0.25" quick-connect tabs, making it easy to prototype and swap. For heavy 240V split-phase HVAC compressors exceeding 30A, step up to the Eaton C25DND230A (30A, 2-pole, 24V coil) definite purpose contactor.






