Full Load Amps (FLA) is the maximum continuous current a motor is designed to draw from the power supply while delivering its rated nameplate horsepower at rated voltage and frequency. When you are wiring a specific heavy-duty machine like the U.S. Motors D20P1G—a 20 HP, 3-phase, 575V NEMA premium efficiency motor—understanding its exact FLA is the single most critical factor for sizing your branch circuit conductors, overload relays, and short-circuit protection. Getting this number wrong doesn't just trip breakers; it causes premature insulation failure, melted terminal lugs, and nuisance downtime on the plant floor.
The Core Concept: What 575V Full Load Amps Actually Means
In a real circuit, the FLA dictates the physical copper thickness in your conduit and the magnetic trip threshold of your breaker. It is the thermal baseline for the motor's windings. If a motor operates continuously above its FLA, the heat generated by I²R losses in the copper windings exceeds the motor's ability to dissipate it, eventually degrading the enamel insulation and causing a phase-to-phase or phase-to-ground fault.
- Locked Rotor Amps (LRA): The massive inrush current drawn when the rotor is stationary and voltage is applied (typically 600% of FLA). Think of FLA like the continuous cruising RPM of a truck pulling a max-weight trailer up a steady 5% grade—it is the thermal limit the engine can sustain indefinitely. LRA is the massive torque spike needed to get that same trailer moving from a dead stop.
- Service Factor Amps (SFA): The current drawn when the motor is operating at its service factor (e.g., 1.15). SFA is higher than FLA and is used for sizing overloads, but not for sizing branch circuit conductors.
- No-Load Amps: The current drawn when the motor is spinning freely with no mechanical load attached (usually 20-30% of FLA).
U.S. Motors D20P1G Spec Sheet and 575V Motor Data
The U.S. Motors D20P1G (manufactured by Nidec) is a staple in heavy industrial and Canadian manufacturing environments where 575V 3-phase is the standard distribution voltage. Below is a data-dense reference table comparing the D20P1G's 20 HP class against adjacent NEMA frame sizes at 575V. Note the critical distinction between the NEC Table value (used for wire/breaker sizing) and the Nameplate value (used for overload sizing).
| HP Rating | Voltage | NEC Table 430.250 FLA | Typical Nameplate FLA | Locked Rotor Amps (LRA) | NEMA Frame |
|---|---|---|---|---|---|
| 15 HP | 575V | 16.0 A | 15.8 A | ~96 A | 254T |
| 20 HP (D20P1G Class) | 575V | 21.0 A | 21.2 A | ~127 A | 256T |
| 25 HP | 575V | 26.0 A | 25.5 A | ~156 A | 284T |
| 30 HP | 575V | 31.0 A | 30.8 A | ~186 A | 324T |
Data sourced from standard NEMA MG-1 efficiency tables and U.S. Motors / Nidec premium efficiency specifications. Always verify against the physical nameplate on your specific unit.
Worked Example: Sizing Wire and Breakers for the D20P1G
Let's run the exact math for installing a U.S. Motors D20P1G (20 HP, 575V, 3-Phase) using NEC Article 430 guidelines. We will assume a standard 1.15 Service Factor and 75°C rated terminations at both the breaker and the motor peckerhead.
NEC Table 430.250 FLA = 21.0 A
Nameplate FLA = 21.2 A
1. Branch Circuit Conductor Sizing (NEC 430.22)
Conductors must be sized at 125% of the NEC Table FLA (not the nameplate).
21.0 A × 1.25 = 26.25 A
Looking at the 75°C column of NEC Table 310.16, 10 AWG THHN copper is rated for 35A. Therefore, 10 AWG copper is the minimum legal wire size. (Do not use the 90°C column for ampacity unless your terminations are explicitly rated for 90°C, which most industrial motor starters and breakers are not).
2. Overload Protection Sizing (NEC 430.32)
Overloads protect the motor windings from slow thermal destruction and are sized based on the Nameplate FLA. For a motor with a 1.15 Service Factor, the maximum setting is 115% of nameplate FLA.
21.2 A × 1.15 = 24.38 A
Set the dial on your bi-metallic or solid-state overload relay to 24.4 A.
3. Short-Circuit and Ground-Fault Breaker Sizing (NEC 430.52)
The branch circuit breaker protects the wire from short circuits, not the motor from overloads. For an inverse-time breaker, the NEC allows up to 250% of the Table FLA to accommodate the LRA inrush without nuisance tripping.
21.0 A × 2.50 = 52.5 A
Per NEC 240.6, you round up to the next standard breaker size. The correct breaker is a 60A, 3-pole, 600V rated molded case circuit breaker (MCCB).
For more on the nuances of motor circuit calculations, the NFPA 70 (National Electrical Code) Article 430 remains the definitive authority, though local AHJs in Canada will default to the Canadian Electrical Code (CEC) Section 28, which uses nearly identical 575V sizing logic.
Where You Meet This in Practice
You will interact with the D20P1G's 575V FLA in three specific real-world scenarios:
- VFD Programming and Thermal Modeling: When commissioning an Allen-Bradley PowerFlex or Yaskawa A1000 drive for this motor, the VFD will prompt you for "Motor Nameplate FLA." You must enter 21.2 A, not the NEC table value. The VFD uses this exact number to build an internal software thermal model of the motor windings, replacing the need for physical overload relays.
- Voltage Drop on Long Feeder Runs: 575V systems are heavily used in mining, lumber, and large-scale agriculture where motors are hundreds of feet from the MCC (Motor Control Center). If your D20P1G is 400 feet away, 10 AWG wire will suffer unacceptable voltage drop during startup. You will need to upsize to 8 AWG or 6 AWG to keep the starting voltage above 85% of nominal (488V), ensuring the motor can overcome the LRA torque requirement without stalling.
- MCC Bucket Retrofits: When sliding a new 20 HP motor starter bucket into an existing 575V MCC, the factory-installed current transformers (CTs) and panel ammeters are often scaled for a specific range. If the bucket was previously used for a 10 HP motor, the ammeter faceplate and CT ratio must be swapped out to accurately reflect the 21.2 A full-scale deflection of the D20P1G.
Frequently Asked Questions (FAQ)
Can I use a 50A breaker if I size the wire to 8 AWG?
No. While 8 AWG wire is perfectly safe for 26.25A, a 50A breaker falls below the 250% maximum threshold but might still nuisance trip during the D20P1G's high-inertia starts. More importantly, NEC 430.52 allows you to go up to the 60A standard size to handle the inrush. If you use a 50A breaker and it trips on startup, you are legally permitted to step up to 60A, provided the wire is sized for the motor FLA (which 8 AWG easily covers).
What happens if the 575V supply drops to 540V under load?
Because power (Watts) equals Voltage × Current × Power Factor × Efficiency, a drop in line voltage forces the motor to draw more current to maintain the same 20 HP mechanical output. If the voltage sags by 6%, the FLA will rise by roughly 6-8%. If this pushes the continuous draw past the 24.4A overload setting, the starter will eventually trip to save the windings from thermal damage.
Does the D20P1G draw the same amps on all three phases?
In a perfectly balanced 575V system, yes. However, a voltage unbalance of just 2% across the three phases can cause a current unbalance of 10% to 20% between the lines. If you measure 21A on L1, 22A on L2, and 19A on L3 with a clamp meter, do not assume the motor is failing; check the supply voltage at the MCC bus first.






