A potential transformer (PT), also known as a voltage transformer (VT), is a precision instrument transformer that steps down high system voltages to a standardized, safe secondary voltage—typically 120V or 110V—for metering and protective relaying. What a PT changes in a real installation is the scale and isolation of the voltage signal. It takes a lethal medium-voltage distribution line (like 14,400V) and scales it down so a standard 120V digital panel meter or microprocessor relay can read it, while galvanically isolating the low-voltage control wiring from the high-voltage bus. Unlike a standard step-down distribution transformer meant to deliver kilowatts of power to loads, a PT is designed to deliver mere watts of signal power with extreme phase and ratio accuracy.
Standard Ratings and Accuracy Classes
Selecting the right PT requires matching the system voltage, the required accuracy for your specific application (revenue metering vs. basic indication), and the total burden of the connected instruments. In North America, these parameters are governed by IEEE C57.13 (Standard for Instrument Transformers). Below is a reference table of standard medium-voltage PT specifications commonly found in metal-clad switchgear and padmount transformers.
| Primary Voltage Class | Standard BIL (kV) | Standard Secondary Voltage | Accuracy Class | Standard Burden (VA) | Typical Application |
|---|---|---|---|---|---|
| 5.0 kV | 60 kV | 120V | 0.3 | 35 VA (Burden M) | Industrial unit substations, motor control |
| 15.0 kV | 95 kV | 120V | 0.3 | 75 VA (Burden W) | Utility distribution, commercial switchgear |
| 25.0 kV | 125 kV | 120V | 0.6 | 200 VA (Burden X) | Heavy industrial, large solar interties |
| 34.5 kV | 150 kV | 115V | 1.2 | 200 VA (Burden X) | Sub-transmission, wind farm collector systems |
The Math: Ratios, Burden, and a Worked Example
To use a PT effectively, you must understand the turns ratio and the concept of 'burden.' The ratio dictates how you scale your meter reading back to the primary line voltage. The burden is the total volt-ampere (VA) load placed on the secondary winding by your meters, relays, and the resistance of the connecting wires.
Worked Numeric Example: 15kV System Metering
Imagine you are commissioning a 15kV switchgear lineup. The installed PT has a primary rating of 14,400V and a secondary rating of 120V.
- Calculate the Ratio: 14,400V / 120V = 120:1 ratio.
- Read the Secondary: Your digital multimeter reads 118.2V on the secondary terminals.
- Scale to Primary: 118.2V × 120 = 14,184V on the actual utility bus.
Now, let's verify the burden to ensure our 0.3 accuracy class is maintained. The PT nameplate is rated for 75VA (Burden W). We must sum the loads:
- Power Quality Meter: 12 VA
- Protective Relay (Voltage Input): 2 VA
- Analog Panel Voltmeter: 15 VA
- Wire Loss (100 ft of 12 AWG copper): ~4 VA
- Total Connected Burden: 33 VA
Because 33 VA is well below the 75 VA nameplate limit, the PT will operate within its 0.3% accuracy band. If you were to add three more analog meters and push the burden to 85 VA, the core would saturate slightly, the phase angle would shift, and your revenue metering would become legally invalid.
Where You Meet Potential Transformers in Practice
You will rarely find PTs in residential or standard commercial 120/208V panels. They live almost exclusively in medium-voltage (MV) and high-voltage (HV) environments. Common locations include:
- Metal-Clad Switchgear: Draw-out PT trucks (like those in Eaton VCP-W or ABB UniGear lineups) allow operators to rack the PT out for secondary injection testing while the main bus remains energized.
- Utility Revenue Metering Cabinets: Outdoor padmount or pole-top enclosures where the utility measures the power delivered to a large industrial facility.
- Renewable Interties: At the point of common coupling (PCC) for large solar farms or battery energy storage systems (BESS), PTs provide the voltage reference for the grid-tie inverters and the utility's revenue meter.
What People Commonly Confuse PTs With
Misidentifying instrument transformers can lead to catastrophic safety hazards. Here is what PTs are frequently confused with, and why the distinction matters:
1. Current Transformers (CTs): CTs step down current (e.g., 600A primary to 5A secondary) and are wired in series with the load. The Golden Rule: A CT secondary must never be open-circuited while primary current flows (it will generate lethal, explosive voltages). A PT secondary must never be short-circuited (it will draw massive fault currents and explode).
2. Control Power Transformers (CPTs): CPTs also step down medium voltage to 120V, but they are designed to supply heavy, noisy loads like breaker closing coils, space heaters, and control relays. CPTs do not maintain strict phase or ratio accuracy. Never use a CPT for revenue metering, and never use a PT to power a breaker coil.
3. Capacitive Voltage Transformers (CVTs): At extra-high voltages (EHV) above 100kV, magnetic PTs become too massive, heavy, and expensive. CVTs use a capacitive voltage divider stack combined with a small intermediate transformer to achieve the same 120V secondary signal. If you are working on 138kV+ transmission lines, you are dealing with CVTs, not magnetic PTs.
Common Questions on PT Selection and Wiring
Do I need to fuse the secondary of a Potential Transformer?
Yes, in almost all applications. While the primary side is protected by the main bus overcurrent devices, the secondary wiring is typically 14 AWG or 12 AWG, which cannot handle the fault current if a short occurs. You must install secondary fuses (or miniature circuit breakers) rated for the wire ampacity and the PT's continuous thermal rating. However, if the PT is dedicated solely to a critical protective relay, some utility standards (like those verified by NETA testing protocols) prohibit secondary fuses to prevent a blown fuse from blinding the relay during a fault.
Why is the secondary circuit grounded?
Safety and noise immunity. Grounding one leg of the secondary (usually X2) ensures that if the internal insulation between the 14,400V primary and the 120V secondary breaks down, the fault current has a direct path to earth, tripping the primary protection rather than energizing the control panel chassis. It also provides a common reference plane, preventing capacitive coupling from inducing erratic, floating voltages on the metering wires.
Can I wire two PTs in an open-delta configuration?
Yes. On three-phase systems, you can use two single-phase PTs wired in an open-delta (V-V) configuration to derive all three phase-to-phase voltages. This is highly common in 15kV and 25kV switchgear to save space and cost. However, you cannot derive a true phase-to-neutral voltage from an open-delta bank, meaning it is unsuitable for applications requiring precise zero-sequence voltage measurement for ground-fault relaying.






