The D20P1G full load amps (FLA) at 575V refers to the maximum continuous current (typically 22A) that this specific 20-horsepower, 3-phase industrial motor draws when operating at its rated mechanical load and nominal 575-volt supply. This single data point changes everything about your installation: it dictates the minimum wire gauge, the inverse-time breaker size, and the thermal overload relay settings required to keep the branch circuit safe and code-compliant. What people most commonly confuse this with is Locked Rotor Amps (LRA) or the physical nameplate amperage, which serve entirely different purposes in circuit design.
Decoding the D20P1G Nameplate and 575V Systems
To properly size components, you first need to understand the environment the D20P1G operates in. The 575V rating is the standard nominal utilization voltage for 600V distribution systems. This is the standard industrial and commercial voltage in Canada, as well as in heavy US industries like mining, water treatment, and large-scale manufacturing. Utilities deliver 600V, but equipment nameplates are stamped at 575V to account for the standard 2.5% to 5% voltage drop across the facility's feeders and transformers.
Why use a 575V motor instead of a standard 480V model? Physics. By pushing the voltage higher, the current drops. A standard 20HP motor at 460V pulls roughly 27A. By stepping up to the 575V / 22A configuration of the D20P1G, you reduce the current by nearly 20%. This lower amperage allows you to use smaller, less expensive conductors and reduces I²R (heat) losses over long wire runs.
According to Fluke's guide on motor nameplate basics, the FLA printed on the physical motor tag is the actual measured current at rated load and exact nameplate voltage. However, as we will cover in the sizing example, the National Electrical Code (NEC) requires you to use standardized table values—not the physical nameplate value—for sizing your branch circuit conductors.
Where You Meet This in Practice
You will typically encounter the D20P1G and similar 575V 20HP motors in three specific scenarios:
- Industrial Exhaust and Make-Up Air Units: Large roof-mounted fans in manufacturing plants where long wire runs from the main switchgear make the lower 22A draw highly advantageous for voltage drop mitigation.
- Heavy-Duty Pump Stations: Municipal water and wastewater lift stations that utilize 600V service entrances to run multiple submersible or vertical turbine pumps.
- Commercial HVAC Chillers: Large centrifugal or screw compressors where the 575V supply keeps the starter contactors and busbars physically smaller than they would need to be at 480V.
In these environments, ambient temperature is a major factor. If your D20P1G is mounted on a roof where ambient temperatures regularly exceed 86°F (30°C), the ampacity of your chosen wire must be derated according to NEC Table 310.15(B)(1)(1). A 10 AWG THHN wire might be mathematically sufficient at room temperature, but in a 110°F rooftop junction box, its ampacity drops, potentially forcing you to upsize to 8 AWG.
Worked Example: Sizing Wire and Breakers for the D20P1G
Let's run the exact math for a standard installation. We are wiring a 20HP, 3-phase, 575V D20P1G motor located 50 feet from the motor control center (MCC). The terminals on both the breaker and the motor starter are rated for 75°C.
Step 1: Find the NEC Table FLA
NEC Article 430.6(A)(1) strictly mandates that you use the tables in Part XIV of Article 430 to size conductors and branch circuit short-circuit devices, not the nameplate. Looking at NEC Table 430.250, the 600V column (which covers 575V nominal systems) lists the Full-Load Current for a 20HP 3-phase motor as 22 Amps.
Step 2: Size the Branch Circuit Conductors
Per NEC 430.22, conductors must be sized at 125% of the motor's Table FLA.
22A × 1.25 = 27.5 Amps.
Looking at the 75°C column of NEC Table 310.16, a 10 AWG copper THHN conductor is rated for 35 Amps. Since 35A > 27.5A, 10 AWG copper is our minimum wire size (assuming standard 30°C ambient temperature).
Step 3: Size the Short-Circuit and Ground-Fault Breaker
Per NEC 430.52, the maximum rating for an inverse-time circuit breaker protecting a standard AC motor is 250% of the Table FLA.
22A × 2.50 = 55 Amps.
Because 55A is not a standard breaker size listed in NEC 240.6, we are permitted to round up to the next standard size. Therefore, we select a 60 Amp, 3-pole inverse-time breaker.
Step 4: Size the Thermal Overload Relay
This is the only place where the physical nameplate matters. The overload relay protects the motor from burning out under mechanical strain. Assume the physical nameplate on your specific D20P1G reads 20.8A with a 1.15 Service Factor. Per NEC 430.32(A)(1), for a motor with a 1.15 SF, the overload is sized at 125% of the nameplate FLA.
20.8A × 1.25 = 26 Amps. You will dial the bimetallic overload relay or select the heater element to trip at 26A.
Decision Tree: Overloads, Breakers, and Conductor Sizing
Use this decision matrix to finalize your bill of materials for the D20P1G installation. This path terminates in the exact parts you need to pull from the stockroom.
| Component | NEC Sizing Rule | Calculation (20HP @ 575V) | Final Concrete Pick |
|---|---|---|---|
| Branch Circuit Wire | 125% of Table 430.250 FLA | 22A × 1.25 = 27.5A | 10 AWG THHN Copper (3-conductor + ground) |
| Short-Circuit Breaker | 250% of Table FLA (Inverse Time) | 22A × 2.5 = 55A (round up) | 60A 3-Pole Molded Case Breaker (MCCB) |
| Motor Starter Contactor | Must handle Table FLA continuously | 22A minimum (NEMA Size 1 or 2) | NEMA Size 2 Contactor (Rated 45A at 575V) |
| Thermal Overload Relay | 125% of Nameplate FLA (1.15 SF) | 20.8A × 1.25 = 26A | Class 10 or 20 Bimetallic Overload (24-28A range) |
Common Confusions: FLA vs. LRA and NEC Table Values
The most frequent mistake junior electricians and DIYers make when wiring high-voltage 3-phase motors is confusing Full Load Amps (FLA) with Locked Rotor Amps (LRA). LRA is the massive inrush current the motor draws the exact millisecond power is applied before the rotor begins to turn. For a 20HP 575V motor, the LRA can easily exceed 130 Amps. If you sized your breaker for FLA (22A), the breaker would instantly trip every time you tried to start the motor. The 250% multiplier in NEC 430.52 exists specifically to allow the breaker to ignore this brief LRA inrush while still protecting the wire from sustained short circuits.
The second major confusion is the Nameplate vs. Table trap. As detailed in ECMag's breakdown of NEC Article 430, the physical nameplate FLA is an empirical test value specific to that exact motor's efficiency and power factor. If you size your wire based on a nameplate that reads 19A, you might install 12 AWG wire. But if that motor is later replaced by a less efficient model that draws 24A at the same 20HP load, the 12 AWG wire will overheat and melt. By legally mandating the use of the standardized NEC Table (22A) for wire sizing, the code ensures the circuit remains safe regardless of what specific motor brand is bolted to the equipment later.
Frequently Asked Questions
Q: My facility voltage is sagging to 540V. Will the D20P1G draw more current?
A: Yes. A 3-phase induction motor acts as a constant-power device. If the voltage drops by 6%, the current will increase by roughly 6% to maintain the 20HP mechanical output. This pushes your 22A load closer to 23.5A, which is why sizing your wire at 125% of the table value provides a necessary thermal buffer for brownout conditions.
Q: Can I use a Variable Frequency Drive (VFD) with this 575V motor?
A: Absolutely, but ensure the VFD is specifically rated for 600V class (575V nominal) input. If you feed a standard 480V VFD with 575V utility power, you will instantly destroy the DC bus capacitors. When using a VFD, the drive's internal software handles the overload protection, but you still must size the input conductors to the VFD based on 125% of the drive's rated input current, not the motor's FLA.






