For a standard 100-amp subpanel, use 3 AWG copper or 1 AWG aluminum wire with a 100A breaker. For a 60-amp subpanel, use 6 AWG copper or 4 AWG aluminum with a 60A breaker. These sizes assume 75°C terminations, 30°C ambient temperature, and THHN/THWN-2 insulation in conduit.
- Material: Copper (primary) and Aluminum (secondary comparison)
- Temperature Column: 75°C (standard for modern breakers and panel lugs per NEC 110.14(C))
- Ambient Temperature: 30°C (86°F) or lower
- Insulation Type: THHN/THWN-2 (90°C rated wire, but ampacity is limited by the 75°C termination rating)
- Installation Method: Raceway (PVC or EMT conduit), maximum 3 current-carrying conductors
The Core Ampacity Table for Subpanel Feeders
When sizing wire for sub panel installations, the National Electrical Code (NEC) requires a 4-wire feeder setup: two hot legs, one neutral, and one equipment grounding conductor. The neutral and ground must remain strictly separated at the subpanel (the main bonding jumper must be removed). The table below provides the minimum wire sizes based on the 75°C column of NEC Table 310.16.
| Subpanel Rating | Max Breaker Size | Copper AWG (75°C) | Aluminum AWG (75°C) | Min PVC Sch 80 Conduit |
|---|---|---|---|---|
| 60A | 6 AWG (65A) | 4 AWG (65A) | 1 inch | |
| 100 Amp | 100A | 3 AWG (100A) | 1 AWG (100A) | 1.25 inch |
| 125 Amp | 125A | 1 AWG (130A) | 1/0 AWG (120A)* | 1.5 inch |
| 150 Amp | 150A | 1/0 AWG (150A) | 2/0 AWG (135A)* | 2 inch |
| 200 Amp | 200A | 2/0 AWG (175A)* | 4/0 AWG (180A)* | 2.5 inch |
*Note: Sizes marked with an asterisk rely on the NEC 240.4(B) 'next size up' rule, which allows you to use the next standard breaker size if the calculated load does not exceed the wire's ampacity and the wire is not part of a multi-outlet branch circuit.
Why These Specific Wire Sizes? (Terminations and NEC Rules)
A common mistake when sizing wire for sub panel feeders is looking at the 90°C column of the ampacity table because THHN wire is rated for 90°C. However, NEC 110.14(C) dictates that the ampacity of a conductor is limited by the lowest temperature rating of any connected termination, conductor, or device. Since almost all modern panelboard lugs and breakers are rated for 75°C, you must use the 75°C column to determine your baseline wire size.
Why not use one size smaller?
Let us look at the 100-amp subpanel row. Why use 3 AWG copper (rated exactly 100A at 75°C) instead of 4 AWG copper? At 75°C, 4 AWG copper is only rated for 85 amps. The standard breaker sizes jump from 80A to 90A to 100A. You cannot protect 85A wire with a 100A breaker under standard feeder rules. While the 'next size up' rule (240.4(B)) allows some flexibility for non-standard ampacities, it does not allow you to jump from 85A all the way to 100A. Therefore, 3 AWG is the absolute minimum for a 100A copper feeder.
Copper vs. Aluminum: Never Interchangeable
Aluminum wire is significantly cheaper and lighter, making it popular for larger feeders (100A and above). However, you cannot simply swap copper for aluminum at the same AWG. Aluminum has higher resistance and expands/contracts more under thermal loading. If you use aluminum, you must:
- Use a wire brush to clean the conductor strands.
- Apply an anti-oxidant compound (like Noalox) to prevent galvanic corrosion and oxide buildup.
- Use a calibrated torque screwdriver to tighten the lugs to the exact inch-pound specification printed on the panel label. Hand-tightening aluminum leads to loose connections, arcing, and fires.
Variables That Force You to Upsize Your Feeder
The table above provides the baseline. But real-world jobsite conditions frequently force you to increase your wire gauge. Use this decision tree to determine if your baseline size is sufficient.
| Variable | Trigger Condition | Required Action |
|---|---|---|
| Voltage Drop | Run length exceeds 80-100 feet at full load. | Upsize wire by 1-2 AWG to maintain <3% drop. |
| Conductor Bundling | More than 3 current-carrying conductors in one conduit. | Apply NEC 310.15(C)(1) derating factors (e.g., 80% for 4-6 conductors). |
| Ambient Heat | Conduit runs through an attic or space >30°C (86°F). | Apply Table 310.15(B)(1) temperature correction factors. |
| Continuous Loads | Subpanel feeds loads expected to run for 3+ hours continuously. | Size wire and breaker at 125% of the continuous load. |
The Voltage Drop Check: A 100-Foot Run
The NEC recommends (but does not strictly mandate for feeders in all cases) a maximum voltage drop of 3% for branch circuits and feeders to ensure equipment operates efficiently. Let us run the math on our 100-amp, 240V subpanel using 3 AWG copper wire over a 100-foot run.
Using the standard voltage drop formula: VD = (2 × K × I × L) / CM
- K (Copper constant) = 12.9
- I (Current) = 100A
- L (One-way length) = 100 ft
- CM (Circular mils for 3 AWG) = 52,620
VD = (2 × 12.9 × 100 × 100) / 52,620 = 4.9 Volts.
Percentage = (4.9 / 240) × 100 = 2.04%.
At 100 feet, 3 AWG copper passes the 3% rule beautifully. But what if your detached garage is 150 feet away? The drop becomes 7.35V (3.06%), which fails the recommendation. According to the Southwire Voltage Drop Calculator and standard field math, you must upsize to 2 AWG copper (CM = 66,360) for a 150-foot run to drop the loss back down to an acceptable 2.43%.
When an Engineer or the AHJ Must Confirm
While this guide covers 95% of residential and light-commercial subpanel feeder scenarios, there are specific edge cases where you must defer to a licensed professional engineer or your local Authority Having Jurisdiction (AHJ):
- Service Entrance vs. Feeder: This guide is strictly for subpanel feeders (downstream of the main service disconnect). If you are sizing the main service entrance conductors from the utility meter to the main panel, different rules apply (such as NEC 310.12 for dwelling services), and the utility company's specifications will override general NEC tables.
- Complex Derating Scenarios: If you are running multiple subpanel feeders through a single underground conduit bank, or routing conduit across a roof where solar gain pushes the ambient temperature to 50°C+, the叠加 (stacking) of temperature correction and bundling derating factors can drastically reduce ampacity. An engineer should perform the exact thermal calculations.
- High Fault Current Availability: If your utility transformer supplies a massive amount of available fault current (e.g., over 22,000 Amps), standard 10kAIC breakers may be inadequate. The AHJ will require you to verify the Short Circuit Current Rating (SCCR) of the subpanel and potentially specify current-limiting fuses or higher-rated breakers, which can change your termination temperature assumptions.
Always pull a permit for subpanel installations. The local electrical inspector will verify your wire sizing, torque marks on the lugs, and ensure the neutral-to-ground bonding screw has been properly removed at the subpanel to prevent objectionable neutral current from flowing on your equipment grounding conductors.






