The most common house wire sizes for standard 120V and 240V branch circuits are 14 AWG (15 amps), 12 AWG (20 amps), and 10 AWG (30 amps). However, when sizing feeders for subpanels, electric vehicle chargers, or heavy appliances, you must reference the official ampacity tables. This guide provides the complete house wire size chart for copper conductors, directly aligned with the National Electrical Code (NEC) standards.

The Complete House Wire Size Chart (NEC Table 310.16)

The table below details the allowable ampacities for insulated copper conductors rated up to 2000 volts. Assumptions: This data assumes copper conductors (THHN, THWN-2, XHHW) in an ambient temperature of 30°C (86°F) with not more than three current-carrying conductors in a single raceway or cable.

How to read this table: The NEC provides three temperature columns. The 60°C column is the legal baseline for smaller wires. The 75°C column applies to most modern residential breakers and terminations. The 90°C column is used exclusively for derating calculations (adjusting for heat or bundling), not for final breaker sizing.
Source: NEC Table 310.16 (Copper Conductors, 30°C Ambient)
AWG / kcmil 60°C (140°F) 75°C (167°F) 90°C (194°F) Common Residential Application
14 AWG 15A 20A 25A Lighting circuits, standard receptacles (15A max breaker)
12 AWG 20A 25A 30A Kitchen/bathroom small appliance circuits (20A max breaker)
10 AWG 30A 35A 40A Electric dryers, window AC units (30A max breaker)
8 AWG 40A 50A 55A Electric ranges, 50A EV chargers (Level 2)
6 AWG 55A 65A 75A 60A subpanel feeders, tankless water heaters
4 AWG 70A 85A 95A 80A-90A heavy feeders, large HVAC compressors
3 AWG 85A 100A 110A 100A main service or subpanel feeders
2 AWG 95A 115A 130A 100A-125A feeders (voltage drop mitigation)
1 AWG 110A 130A 150A 125A subpanel feeders
1/0 AWG 125A 150A 170A 150A residential service entrance
2/0 AWG 145A 175A 195A 200A residential service entrance (short runs)
3/0 AWG 165A 200A 225A 200A service entrance (standard for long runs)
4/0 AWG 195A 230A 260A 200A service with heavy voltage drop compensation

How to Read This Chart: Columns, Derating, and Limits

Looking up a number in the house wire size chart is only the first step. To legally and safely size your wire, you must understand how the NEC restricts the values in those columns.

Which Column Applies to Your Installation?

Under NEC 110.14(C), the ampacity of a wire is limited by the lowest temperature rating of any connected termination, conductor, or device. Most modern residential circuit breakers and receptacles are rated for 75°C. However, the NEC enforces a strict exception for small conductors: 14, 12, and 10 AWG wires must always be sized using the 60°C column for their final overcurrent protection, regardless of the insulation's 90°C rating. Furthermore, NEC 240.4(D) hard-caps the breaker size for these small wires at 15A, 20A, and 30A respectively.

Safety Caveat: Never install a 20A breaker on 14 AWG wire, even if a specific device termination is rated 75°C. The 15A hard limit for 14 AWG is an absolute safety rule to prevent concealed wire fires.

How Derating Rows Modify the Base Value

The 90°C column exists primarily for derating. If you pull more than three current-carrying conductors through a single conduit, or if the ambient temperature in your attic exceeds 30°C (86°F), you must multiply the 90°C ampacity by a correction factor.

Worked Example: You are pulling four current-carrying 10 AWG THHN wires through a conduit to a detached garage. According to NEC Chapter 9, Table 310.15(C)(1), four conductors require an 80% derating factor. You look at the 90°C column for 10 AWG (40A) and multiply by 0.80, resulting in a derated ampacity of 32A. Because 32A is not a standard breaker size, you step down to the next standard size: a 30A breaker.

What the Table Cannot Tell You: Voltage Drop

This chart assumes a short wire run. It does not account for voltage drop. If you use 4 AWG copper to feed a 60A subpanel 150 feet away, the wire can safely handle the heat (ampacity), but the resistance over that distance will cause the voltage to sag below 114V under load. This sag can damage sensitive electronics and cause motors to overheat. For runs over 100 feet, always calculate voltage drop and upsize your wire by one or two AWG steps beyond what the ampacity chart demands.

Frequently Asked Questions About House Wire Sizing

What size wire do I need for a 50 amp breaker?

For a 50-amp breaker (commonly used for Level 2 EV chargers, hot tubs, or small subpanels), you must use 6 AWG copper wire. Looking at the 75°C column, 6 AWG is rated for 65A, which safely covers the 50A continuous or non-continuous load. If you are using aluminum wire (like SER cable), you must step up to 4 AWG aluminum, as aluminum has a higher resistance and lower ampacity per AWG than copper.

Can I use 14 AWG wire on a 20 amp breaker?

No. Under NEC 240.4(D), 14 AWG copper wire is strictly limited to a maximum overcurrent protective device (breaker or fuse) of 15 amps. If you wire a 20A circuit with 14 AWG, the breaker will not trip before the wire overheats and melts the insulation inside the walls. You must use 12 AWG or larger for any 20A circuit.

What wire size is required for a 100 amp subpanel feeder?

For a 100-amp subpanel, you need 3 AWG copper or 1 AWG aluminum (rated in the 75°C column). However, if the subpanel is located in a detached garage more than 100 feet away from the main panel, you should upsize to 2 AWG copper or 1/0 AWG aluminum to mitigate voltage drop. Always ensure your equipment grounding conductor is sized according to NEC Table 250.122 (an 8 AWG copper ground is required for a 100A feeder).

Does the ground wire need to be the same size as the hot wires?

No, the equipment grounding conductor (EGC) is typically smaller than the current-carrying conductors. Its only job is to carry fault current long enough to trip the breaker. For example, on a 30A circuit using 10 AWG hot wires, an 8 AWG copper ground is sufficient. On a 100A feeder using 3 AWG hot wires, an 8 AWG copper ground is also the minimum requirement. Refer to NEC Table 250.122 for exact grounding sizes based on your breaker rating.