When sizing conductors for residential or commercial branch circuits and feeders, the AWG current rating chart—specifically derived from NEC Table 310.16—is your master reference. This chart dictates the maximum continuous current a wire can carry before its insulation begins to degrade. However, simply matching your breaker size to the highest number on the chart is a fast track to a failed inspection or a melted terminal lug. The correct ampacity depends on your wire material, insulation type, termination temperature ratings, and conduit fill.
Below is the complete reference data for copper and aluminum conductors, followed by the jobsite rules for applying these numbers to your actual installation.
The Complete AWG Current Rating Chart (NEC Table 310.16)
How to read this table: This data is sourced directly from the NFPA 70 National Electrical Code (NEC) Table 310.16. The values assume an ambient temperature of 30°C (86°F) and not more than three current-carrying conductors in a raceway. The columns are split by the temperature rating of the wire insulation (60°C, 75°C, and 90°C). Common 90°C wires include THHN and XHHW-2, while older NM-B (Romex) is typically rated for 60°C or 90°C depending on the manufacturing year, though its ampacity is legally capped at the 60°C column for standard residential use.
| AWG / kcmil | Cu 60°C (140°F) | Cu 75°C (167°F) | Cu 90°C (194°F) | Al 60°C (140°F) | Al 75°C (167°F) | Al 90°C (194°F) |
|---|---|---|---|---|---|---|
| 14 AWG | 15A | 20A | 25A | — | — | — |
| 12 AWG | 20A | 25A | 30A | 15A | 20A | 25A |
| 10 AWG | 30A | 35A | 40A | 25A | 30A | 35A |
| 8 AWG | 40A | 50A | 55A | 30A | 40A | 45A |
| 6 AWG | 55A | 65A | 75A | 40A | 50A | 55A |
| 4 AWG | 70A | 85A | 95A | 55A | 65A | 75A |
| 3 AWG | 85A | 100A | 110A | 65A | 75A | 85A |
| 2 AWG | 95A | 115A | 130A | 75A | 90A | 100A |
| 1 AWG | 110A | 130A | 145A | 85A | 100A | 115A |
| 1/0 AWG | 125A | 150A | 170A | 100A | 120A | 135A |
| 2/0 AWG | 145A | 175A | 195A | 115A | 135A | 150A |
| 3/0 AWG | 165A | 200A | 225A | 130A | 155A | 170A |
| 4/0 AWG | 195A | 230A | 260A | 150A | 180A | 205A |
Which Temperature Column Applies to Your Installation?
The most common mistake DIYers and junior apprentices make is using the 90°C column simply because they bought THHN wire. The NEC enforces a "weakest link" rule under NEC 110.14(C). Your allowable ampacity is limited by the lowest temperature rating of any connected device, termination, or conductor in the circuit.
Almost all standard residential circuit breakers, receptacles, and switches are rated for 75°C terminations. Therefore, even if your THHN wire is rated for 90°C, you must size your overcurrent protection based on the 75°C column.
Furthermore, for conductors sized 14, 12, and 10 AWG, NEC 110.14(C)(1)(a) mandates that you must use the 60°C column for ampacity sizing in standard residential applications, regardless of the wire's insulation rating. This is why 14 AWG NM-B and 14 AWG THHN are both universally capped at 15 amps.
How Derating Factors Modify Base Ampacity & Chart Limitations
The AWG current rating chart above assumes ideal conditions: an ambient temperature of 30°C (86°F) and a maximum of three current-carrying conductors in a single raceway. When real-world jobsite conditions deviate, you must apply derating factors.
Applying Conduit Fill and Ambient Temperature Derating
If you pull four to six current-carrying conductors through a single conduit, NEC Table 310.15(C)(1) requires you to derate the wire's ampacity to 80% of its base value. If you pull seven to nine conductors, you derate to 70%.
The Pro Calculation Method: When derating for conduit fill or high ambient temperatures, you apply the derating multiplier to the 90°C column (because the wire's insulation can physically handle the heat). However, the final derated number cannot exceed the ampacity listed in the termination temperature column (usually 75°C).
Example: You have four 8 AWG copper THHN current-carrying conductors in a conduit. The 90°C column lists 55A. Multiplying 55A by the 80% derating factor yields 44A. Because 44A is less than the 75°C termination limit of 50A, your final allowable ampacity is 44A. You would protect this circuit with a 40A breaker.
What the AWG Current Rating Chart Cannot Tell You
Ampacity is only half the battle. The chart provides zero guidance on:
- Voltage Drop: A 12 AWG wire can safely carry 20A indefinitely, but if that run is 150 feet long to a shed, the voltage drop will exceed the recommended 3% threshold, causing motors to overheat and lights to dim. For long runs, use a dedicated voltage drop calculator and upsize the wire.
- Short-Circuit Withstand: The chart doesn't tell you if the wire can survive the thermal stress of a massive short-circuit event before the breaker trips. This is governed by different engineering tables.
- Physical Pulling Tension: When pulling large aluminum feeders (like 4/0 AWG) through long conduit runs with bends, the physical pulling tension can stretch and damage the conductor if not calculated and managed with proper lubricants.
AWG Current Rating Chart FAQ
What size breaker do I use for 10 AWG wire?
For standard residential branch circuits, the maximum breaker size for 10 AWG copper wire is 30 amps. This is strictly enforced by NEC 240.4(D). While 10 AWG copper has a higher raw ampacity in the 75°C and 90°C columns, the small conductor rule caps the overcurrent protection device at 30A to prevent the wire from overheating at the termination points.
Can I use the 90°C column for sizing my breaker?
No, not for standard terminations. You can only use the 90°C column as a starting point for applying derating factors (like conduit fill or high ambient temperatures). The final allowable ampacity used to select your breaker must never exceed the value in the temperature column that matches your equipment's termination rating, which is almost always 75°C for modern breakers and 60°C for small conductors (14-10 AWG).
Does the AWG current rating chart apply to DC solar wiring?
Yes, the thermal ampacity limits in NEC Table 310.16 apply to DC conductors just as they do to AC. However, in low-voltage DC solar systems (12V, 24V, or 48V), voltage drop is the primary limiting factor, not thermal ampacity. A wire that is thermally rated for 30A might cause an unacceptable 15% voltage drop on a 12V system over a 20-foot run, requiring you to upsize the wire by several AWG sizes to maintain system efficiency.
How does bundling wires in a conduit change the chart values?
When you bundle more than three current-carrying conductors in a single conduit or cable, the heat generated by each wire traps heat in the adjacent wires. To prevent insulation meltdown, NEC Table 310.15(C)(1) requires you to multiply the base ampacity (from the 90°C column) by a derating percentage. For 4-6 wires, multiply by 80%; for 7-9 wires, multiply by 70%. Note that grounding wires and neutral wires that only carry unbalanced current do not count toward this total.






