For a standard 100A 3-phase circuit in the US, you need 3 AWG copper wire (assuming 75°C rated terminals). The required insulation colors depend entirely on your system voltage: a 208Y/120V system uses Black, Red, and Blue; a 480Y/277V system uses Brown, Orange, and Yellow; and a 240V High-Leg Delta uses Black, Orange (high leg), and Blue. Sizing and coloring 3-phase feeders requires cross-referencing ampacity tables with voltage-specific color codes to pass inspection and prevent catastrophic cross-voltage wiring errors.

The 3-Phase Wire Color and Ampacity Chart (Up to 100A)

The table below merges copper wire ampacity limits with mandatory phase conductor colors. How to read this table: Locate your target amperage in the 60°C or 75°C column (see the next section to determine which applies). Read left to find the minimum AWG size, then read right to select the correct THHN/THWN-2 insulation colors based on your facility's nominal voltage.

Data sourced from NFPA NEC Table 310.16 (Ampacities of Insulated Conductors) and NEC Articles 215.12, 230.56, and 210.4 (Color Codes and High-Leg Identification).

AWG Size (Cu) 60°C Ampacity 75°C Ampacity 208Y/120V Colors 480Y/277V Colors 240V High-Leg Colors
1415A20ABlk / Red / BluBrn / Org / YelBlk / Org / Blu
1220A25ABlk / Red / BluBrn / Org / YelBlk / Org / Blu
1030A35ABlk / Red / BluBrn / Org / YelBlk / Org / Blu
840A50ABlk / Red / BluBrn / Org / YelBlk / Org / Blu
655A65ABlk / Red / BluBrn / Org / YelBlk / Org / Blu
470A85ABlk / Red / BluBrn / Org / YelBlk / Org / Blu
385A100ABlk / Red / BluBrn / Org / YelBlk / Org / Blu
295A115ABlk / Red / BluBrn / Org / YelBlk / Org / Blu
1110A130ABlk / Red / BluBrn / Org / YelBlk / Org / Blu

Decoding the Columns: Temperature Ratings and Derating

Which column applies to your installation? Under NEC 110.14(C)(1)(a), if your circuit is rated 100A or less, you must default to the 60°C column unless the breaker and equipment terminals are explicitly marked for 75°C. Most modern 100A molded-case breakers (like Square D PowerPact or Eaton FD series) are rated 75°C, allowing you to use the 75°C column (3 AWG for 100A). If you are connecting to older equipment, unmarked lugs, or NM-B cable, you are legally bound to the 60°C column, requiring 1 AWG for a 100A load.

How derating rows modify the base value: The ampacities above assume no more than three current-carrying conductors in a raceway and an ambient temperature of 30°C (86°F). If you pull two 3-phase circuits in a single conduit (6 current-carrying conductors), OSHA Standard 1910.304 and NEC 310.15(C)(1) mandate an 80% derating factor. A 3 AWG wire rated at 100A drops to 80A (100 x 0.80). To maintain a legal 100A capacity under these conditions, you must upsize to 1 AWG copper (130A x 0.80 = 104A).

Decision Tree: Picking Your Exact Wire and Color

Use this decision path to terminate your planning phase with a concrete materials list. Trace your system voltage down to the final pick.

System Voltage Configuration Phase Colors Required Neutral & Ground Concrete 100A Pick (75°C)
208Y/120V Standard Commercial Wye Black, Red, Blue White (Neu), Green (Gnd) 3 AWG THHN (5 wires total)
480Y/277V Industrial / Lighting Wye Brown, Orange, Yellow Gray (Neu), Green (Gnd) 3 AWG THHN (5 wires total)
240/120V High-Leg Delta Black, Orange*, Blue White (Neu), Green (Gnd) 3 AWG THHN (5 wires total)

*Note: In a High-Leg Delta, the Orange wire MUST be the high leg (208V to neutral) and must be tagged or durably marked at every termination point per NEC 230.56.

Default Recommendation: If you are feeding a standard 100A 208V 3-phase commercial subpanel with modern 75°C breakers and a standard 3-conductor pull, buy 3 AWG Copper THHN in Black, Red, Blue, White, and Green. Do not substitute aluminum without upsizing to 1/0 AWG.

What This Chart Cannot Tell You (Edge Cases & Code Limits)

While the chart above satisfies NEC ampacity and identification rules, it omits three critical engineering variables that dictate real-world performance:

  • Voltage Drop Over Distance: NEC 310.15(B) provides an informational note recommending a maximum 3% voltage drop for feeders. At a full 100A load on a 208V 3-phase circuit, 3 AWG copper will hit a 3% drop at approximately 115 feet. If your conduit run is 150 feet, 3 AWG is legally allowable for ampacity but practically insufficient; you must upsize to 1/0 AWG to prevent motor overheating and dimming lights.
  • Aluminum vs. Copper: This chart strictly applies to copper. If you are using aluminum conductors (like XHHW-2 AL) to save money on long feeder runs, the 75°C ampacity for 100A requires a minimum of 1/0 AWG Aluminum, and your color coding rules remain identical.
  • Continuous Loads: If your 3-phase load is continuous (running for 3 hours or more, such as HVAC compressors or industrial lighting), NEC 210.20 requires the branch circuit rating to be 125% of the continuous load. A 100A continuous load requires a 125A breaker and wire sized for 125A (1 AWG Copper at 75°C), not 3 AWG.

Quick-Jump Reference: Most Queried 3-Phase Configurations

Bookmark this section for rapid jobsite lookups. These assume copper wire, 75°C terminals, no derating, and runs under 100 feet.

  • 100A 208V 3-Phase: 3 AWG Cu | Black, Red, Blue, White, Green
  • 100A 480V 3-Phase: 3 AWG Cu | Brown, Orange, Yellow, Gray, Green
  • 60A 208V 3-Phase: 6 AWG Cu | Black, Red, Blue, White, Green
  • 60A 480V 3-Phase: 6 AWG Cu | Brown, Orange, Yellow, Gray, Green
  • 30A 208V 3-Phase: 10 AWG Cu | Black, Red, Blue, White, Green
  • 30A 480V 3-Phase: 10 AWG Cu | Brown, Orange, Yellow, Gray, Green
  • 200A 480V 3-Phase (Bonus): 2/0 AWG Cu | Brown, Orange, Yellow, Gray, Green

Always verify your local Authority Having Jurisdiction (AHJ) requirements, as some municipalities enforce stricter voltage drop limits or mandate specific phase-color taping practices at terminations regardless of the insulation jacket color.