For a standard 100 amp non-continuous load, you need 3 AWG copper or 1 AWG aluminum wire, assuming standard 75°C terminations and an ambient temperature of 30°C (86°F). If the load is continuous (expected to run for 3 hours or more), you must multiply the load by 125%, requiring 1 AWG copper or 1/0 AWG aluminum. These values are dictated by the 75°C column of NEC Table 310.16.
The 100 Amp Breaker Wire Size Chart (NEC Table 310.16)
To use this chart correctly, you must understand the temperature columns. While modern THHN/THWN-2 wire is physically insulated to withstand 90°C, NEC 110.14(C) restricts your final ampacity to the lowest temperature rating of any connected component. Because nearly all residential breakers and panel lugs are rated for 75°C, the 75°C column is your baseline for termination ampacity. The 90°C column is only used as a starting point for derating calculations (explained below).
| AWG Size | Material | 60°C Ampacity | 75°C Ampacity (Termination) | 90°C Ampacity (Derating Base) | Application for 100A Breaker |
|---|---|---|---|---|---|
| 4 AWG | Copper | 70A | 85A | 95A | Undersized (Max 70A-85A) |
| 3 AWG | Copper | 85A | 100A | 110A | Min. for 100A non-continuous |
| 2 AWG | Copper | 95A | 115A | 130A | Allowed (Next size up rule) |
| 1 AWG | Copper | 110A | 130A | 145A | Min. for 100A continuous (125A) |
| 1/0 AWG | Copper | 125A | 150A | 170A | Oversized / Voltage drop mitigation |
| 2 AWG | Aluminum | 75A | 90A | 100A | Undersized for 75°C lugs |
| 1 AWG | Aluminum | 100A | 120A | 135A | Min. for 100A non-continuous |
| 1/0 AWG | Aluminum | 120A | 135A | 150A | Min. for 100A continuous |
Derating, Voltage Drop, and What the Chart Cannot Tell You
The chart above assumes perfect conditions: an ambient temperature of 30°C (86°F) and no more than three current-carrying conductors in a raceway. Real-world jobsites rarely match this. Here is how derating and distance modify your base wire size.
How Derating Modifies the Base Value
When you pull more than three current-carrying conductors through a single conduit, the wires heat each other up. Per NEC Table 310.15(C)(1), you must apply an adjustment factor. This is where the 90°C column becomes useful.
- Scenario: You are pulling two hots, a neutral, and a ground (4 current-carrying conductors) for a 120/240V multi-wire branch circuit or feeder. The adjustment factor is 80%.
- Calculation: You cannot use 3 AWG Copper. Its 90°C rating is 110A. 110A × 0.80 = 88A. An 88A derated ampacity cannot be protected by a 100A breaker.
- The Fix: Step up to 1 AWG Copper. Its 90°C rating is 145A. 145A × 0.80 = 116A. Since 116A > 100A, 1 AWG copper passes the derating requirement and can legally terminate on 75°C lugs.
What the Table Cannot Tell You: Voltage Drop
NEC Table 310.16 only prevents the wire from melting; it does not guarantee your equipment will receive adequate voltage. The Electrical Safety Foundation International (ESFI) and NEC Informational Notes recommend keeping voltage drop under 3% on feeders.
If you are running a 100A subpanel 150 feet away from the main panel, 3 AWG copper will experience roughly a 3.8% drop on 120V circuits at full load. To maintain a strict 3% drop at maximum capacity over that distance, you must ignore the minimum chart requirements and step up to 1/0 AWG copper or 2/0 AWG aluminum.
Frequently Asked Questions
Can I use 2 AWG wire for a 100 amp breaker?
Yes, 2 AWG copper (rated 115A at 75°C) is perfectly legal for a 100A breaker under the NEC "next standard size up" rule (NEC 240.4(B)), provided your calculated load does not exceed 100A. However, 2 AWG is an awkward middle ground: it is more expensive than 3 AWG, but lacks the extra thermal headroom of 1 AWG for continuous loads or voltage drop mitigation. Most electricians will jump straight from 3 AWG to 1 AWG to avoid stocking and pulling the less common 2 AWG size.
Does a 100 amp subpanel need a ground wire, and what size?
Yes. A feeder to a subpanel requires four wires: two hots, one neutral, and one Equipment Grounding Conductor (EGC). Per NEC 250.122, for a 100A overcurrent device, the minimum EGC size is 8 AWG copper or 6 AWG aluminum. Note that the neutral and ground must remain strictly isolated (unbonded) at the subpanel.
Can I use 90°C THHN wire to get a smaller wire size for 100 amps?
No. A common DIY mistake is looking at the 90°C column, seeing that 4 AWG THHN is rated for 95A, and assuming it is "close enough" or trying to use it for a 100A breaker. Because the breaker lugs are rated 75°C, NEC 110.14(C) forces you to use the 75°C column for your final termination ampacity. At 75°C, 4 AWG is only good for 85A. You must use 3 AWG minimum.
How far can I run 100 amp wire before voltage drop requires a larger size?
For a standard 240V load (like an EV charger or large compressor) pulling a full 100A, 3 AWG copper will hit the 3% voltage drop threshold (7.2V drop) at approximately 115 feet. If your run exceeds 115 feet at full continuous load, you must upsize to 2 AWG or 1 AWG copper. For 120V loads, that distance is halved to roughly 55 feet before you need to upsize.






