The standard solenoid symbol in electrical schematics is a rectangle representing the electromagnetic coil, typically labeled with terminals A1 and A2 (IEC) or 1 and 2 (NEMA). Inside the rectangle, a diagonal line indicates an AC coil, while a straight horizontal line or a parallel diode symbol indicates a DC coil. When paired with fluid power valves, ISO 1219 adds square boxes representing valve positions. If you are reading a US-based industrial print, expect NEMA/ANSI Y32.2 symbols; for European or international prints, expect IEC 60617. Below is the definitive reference for identifying, troubleshooting, and replacing these components based on their schematic symbols.

The Complete Solenoid Symbol Reference Table

Use this table to identify the coil type and function directly from the schematic. This covers the most common electromagnetic actuators found in industrial control panels and fluid power systems.

Component Visual Symbol Description IEC 60617 Terminals ANSI/NEMA Terminals Primary Application
Standard DC Solenoid Rectangle with a straight horizontal line inside, or a parallel diode symbol. A1 (+), A2 (-) 1 (+), 2 (-) General purpose relays, 24VDC pneumatic valves.
Standard AC Solenoid Rectangle with a diagonal line (or zigzag) inside. A1, A2 (Polarity independent) 1, 2 (Polarity independent) 120VAC/240VAC contactors, heavy-duty hydraulic valves.
Proportional Solenoid Rectangle with a diagonal arrow crossing through it, or a variable resistor symbol inside. A1, A2 (Analog input) 1, 2 (Analog input) Variable flow/pressure control, requires PWM or analog driver.
Latching (Bistable) Solenoid Rectangle with a mechanical latch symbol (small hook or cross) adjacent to the coil. Set (S), Reset (R) Set, Reset Battery-powered valves, safety shutoffs that must retain state on power loss.
Solenoid Valve (2/2 Way NC) Standard coil symbol attached to an ISO 1219 square box with a diagonal arrow pointing to a closed port. A1, A2 1, 2 Normally closed fluid shutoff; opens only when energized.

Regional and Standard Variants (IEC vs. ANSI vs. ISO)

Reading a schematic requires knowing which drafting standard the engineer used. Mixing up IEC and ANSI conventions can lead to wiring a 24VDC coil to a 120VAC line, instantly destroying the component.

Rule of Thumb: If the schematic uses alphanumeric terminal designations like A1/A2 for coils and 13/14 for NO contacts, you are looking at an IEC 60617 drawing (common in Europe, Asia, and modern global OEMs). If it uses simple numbers like 1/2 for coils and 3/4 for contacts, it is an ANSI/NEMA drawing (common in legacy US and Canadian facilities).

When the solenoid is part of a hydraulic or pneumatic valve assembly, the electrical coil symbol is only half the story. The fluid power ports are drawn using ISO 1219-1 conventions. In ISO 1219, the solenoid coil is drawn as a small rectangle abutting a larger square (the valve spool position). A spring symbol on the opposite side of the square indicates the valve's fail-safe position when the solenoid is de-energized. For a deeper dive into general electrical drafting conventions, the All About Circuits reference guide provides an excellent crosswalk between IEEE 315 (ANSI) and IEC standards.

The Symbols and Rows People Get Wrong

Even experienced technicians misinterpret specific solenoid symbols, leading to incorrect replacements or blown fuses. Watch out for these common pitfalls:

  • The Proportional vs. On/Off Trap: A proportional solenoid symbol looks nearly identical to a standard DC coil, except for a small diagonal arrow or a box labeled "V/I" (voltage/current converter). If you replace a proportional coil with a standard on/off DC coil, the valve will snap violently to 100% open instead of modulating, potentially causing water hammer or over-pressurization.
  • The Missing AC Diagonal Line: On faded blueprints or poorly printed PDFs, the tiny diagonal line inside the AC coil rectangle disappears. The technician assumes it is a DC coil, wires it to a 24VDC power supply, and the valve fails to actuate because the AC coil's impedance is too high at DC to pull the plunger.
  • Integral Suppression Diodes: Many modern DC solenoid symbols include a small triangle-and-line (diode) symbol drawn in parallel with the coil. This indicates an integral flyback diode. If you wire this backward (reverse polarity), you will short-circuit the power supply through the diode and blow the branch fuse instantly.
  • ISO Valve "Boxes": People often count the number of ports on the physical valve and assume that matches the schematic. In ISO 1219, the number of boxes represents the number of states (e.g., 2 boxes = 2-way valve), while the number of lines touching the boxes represents the number of ports.

Safe Interpretation When Markings Are Faded or Missing

On the jobsite, you will frequently encounter solenoids where the nameplate has been painted over, burned off, or chemically degraded. Guessing the voltage based on the physical size of the coil is dangerous; a 24VAC coil and a 120VAC coil can look physically identical.

SAFETY FIRST: Before removing wires or testing a solenoid coil, de-energize the circuit, apply Lockout/Tagout (LOTO), and verify the absence of voltage at the coil terminals using a Category III or IV multimeter. Never test a live coil with an ohmmeter.

Follow this bench-testing procedure to definitively identify an unmarked solenoid coil (assumes standard copper windings at 20°C ambient):

  1. Measure DC Resistance (Ohms): Set your multimeter to the Ohms range.
    • 10Ω to 50Ω: Almost certainly a 24VDC or 12VDC coil. (A 12VDC coil typically reads 10-20Ω; a 24VDC reads 20-50Ω).
    • 150Ω to 500Ω: Likely a 120VAC coil. AC coils rely on inductive reactance to limit current, so their DC resistance is higher than equivalent DC coils.
    • 800Ω to 2000Ω+: Likely a 240VAC coil.
  2. Perform a Diode Test: Set your meter to Diode Test mode and probe the terminals in both directions. If you get a 0.5V to 0.7V drop in one direction and "OL" (open loop) in the other, the solenoid has an integral flyback diode and is strictly DC. Note which terminal is the anode (positive) and mark it.
  3. Check for Shading Rings (AC only): Look closely at the metal plunger or the top of the coil assembly through the casing. If you see a distinct copper ring embedded in the steel pole piece (a shading coil), it is definitively an AC solenoid. DC solenoids do not use shading rings because they do not suffer from AC zero-crossing chatter.

Solenoid Selection Decision Path

When replacing a failed solenoid or designing a new control circuit, use this decision matrix to terminate your search and select the exact component class required.

System Condition / Requirement Required Symbol Feature Action / Specification
Power supply is 24VDC, PLC transistor outputs. DC Coil with integral flyback diode symbol. Specify 24VDC coil with built-in spike suppression to protect PLC outputs.
Power supply is 120VAC, mechanical switch control. AC Coil (diagonal line), no diode required. Specify 120VAC, 60Hz coil. Add an external RC snubber if switching via solid-state relay.
Valve must hold position during a total power failure. Latching (Bistable) solenoid symbol. Specify a dual-coil latching solenoid or a spring-return valve with a mechanical detent.
Process requires variable flow based on 4-20mA signal. Proportional solenoid symbol (diagonal arrow). Specify a proportional coil paired with a dedicated PWM/amplifier driver card.
Unmarked coil measured at ~35Ω, diode test shows 0.6V drop. Standard DC Coil with suppression. Terminate search: Order a standard 24VDC industrial valve coil (e.g., ASCO RedHat WBIS series or Parker equivalent).

Final Concrete Recommendation: If your decision path leads to the most common industrial scenario—a 24VDC, 2-way, normally closed (NC) pneumatic or liquid shutoff valve with a 1/4" NPT port and integral suppression—do not overcomplicate the BOM. Standardize on the ASCO 8262G014 (or its direct modern equivalent in the ASCO 210/310 series). It matches the standard DC solenoid symbol with suppression, handles up to 150 PSI of air/water, and draws roughly 1.6A inrush / 0.8A holding current, making it perfectly compatible with standard 2A PLC transistor outputs and 10 AWG control wiring.