Magnetomotive force (MMF) is the magnetic pressure, measured in ampere-turns, that drives magnetic flux through a magnetic circuit, acting exactly like voltage does in an electrical circuit. When you energize a relay or a motor starter, it is the MMF that generates the physical pulling force required to snap the contacts closed against spring tension. If you are troubleshooting a chattering contactor, a weak solenoid, or a transformer that hums excessively, you are almost always looking at a magnetomotive force deficit.
The Core Definition: What MMF Actually Changes in a Circuit
To properly define magnetomotive force, you have to look at the magnetic equivalent of Ohm's Law. In an electrical circuit, Electromotive Force (EMF, or voltage) pushes current through resistance. In a magnetic circuit, Magnetomotive Force pushes magnetic flux through reluctance. According to Georgia State University HyperPhysics, the relationship is expressed as:
Flux (Φ) = MMF / Reluctance (ℜ)
Think of MMF as the water pressure in a closed plumbing system: the higher the pressure (MMF), the more water (flux) you can force through a narrow, restrictive pipe (reluctance). However, unlike water pressure which is measured in PSI, MMF is calculated by multiplying the number of wire turns in a coil by the current flowing through them.
- Magnetic Flux (Webers): Flux is the result (the actual magnetic field lines). MMF is the cause (the push).
- Magnetic Field Strength (H): Field strength is MMF distributed over a specific distance (Ampere-turns per meter). MMF is the total aggregate force regardless of the core length.
- Inductance (Henries): Inductance is a property of the coil's geometry and core material; MMF is the active force generated only when current flows.
The Math: A Worked Numeric Example for a 24V Contactor
Let's move off the whiteboard and onto the workbench. Suppose you are testing a Siemens 3RT2015 24V DC contactor used to start a 3-phase coolant pump. The coil bobbins on these industrial starters are typically wound with thousands of turns of fine magnet wire (often around 38 AWG) to maximize turns without making the coil physically massive.
Here are the real-world bench measurements for this specific coil:
- Coil Resistance (R): 436 Ω
- Applied Voltage (V): 24V DC
- Number of Turns (N): 4,200 turns
First, we find the current using standard Ohm's Law:
I = V / R = 24V / 436 Ω = 0.055 A (55 mA)
Next, we calculate the Magnetomotive Force:
MMF = N × I = 4,200 turns × 0.055 A = 231 Ampere-turns (At)
Where You Meet MMF in Practice (And When It Fails)
You interact with magnetomotive force every time you wire a control panel, but it becomes highly visible when things break down. Here is where MMF dictates the success or failure of your installation:
1. AC vs. DC Contactor Coils and the 'Chatter' Effect
In a DC circuit, current is constant, so MMF is constant. In an AC circuit, the current crosses zero 120 times a second (on a 60Hz grid). If the MMF drops to zero, the spring tension pushes the contacts open, resulting in a violent 120Hz mechanical chatter that will weld your contacts and burn out the coil. To fix this, AC contactor armatures are fitted with a shading ring (a shorted copper loop). This ring creates a secondary, phase-shifted MMF that keeps the total magnetic pressure above the pull-in threshold even when the main AC current hits zero.
2. Solenoid Valves and Air Gaps
Reluctance is the enemy of MMF. Air is a terrible conductor of magnetic flux (it has high reluctance). When a solenoid valve is fully open, the metal plunger closes the air gap, dropping reluctance and allowing the flux to peak. If debris gets stuck in the valve and leaves a 1mm air gap, the reluctance spikes. The MMF remains the same, but the flux drops drastically, and the solenoid fails to pull the plunger home. The coil then draws continuous inrush current and burns out.
3. Transformer Core Saturation
As detailed in the All About Circuits magnetic circuits guide, pushing too much MMF into a ferromagnetic core leads to saturation. Once all the magnetic domains in the steel core are aligned, increasing the current (and thus the MMF) yields almost zero additional flux. The excess energy turns into heat, which is why over-exciting a transformer or running a 50Hz transformer on a 60Hz VFD output without derating causes catastrophic thermal failure.
Decision Tree: Sizing and Replacing Inductive Coils by MMF
When a coil burns out, you cannot simply swap it with any coil that fits the physical bobbin. You must match the magnetomotive force profile. Use this decision matrix to select your replacement part.
| Condition / Measurement | Diagnostic Result | Action & Concrete Part Pick |
|---|---|---|
| Original coil is AC (e.g., 120VAC) | Armature requires shading ring to prevent 120Hz chatter. | Must use AC coil. Pick exact OEM replacement (e.g., Siemens 3RT2916-1BB40 equivalent AC version). Never substitute DC. |
| Original coil is DC, control voltage is stable at 24V | Standard pull-in MMF required (~200-250 At). | Standard DC Coil. Pick Siemens 3RT2015-1BB41 (24V DC, 7A, built-in surge suppression). |
| Original coil is DC, but control voltage sags below 20V | Standard coil MMF drops below 80% pull-in threshold. | Wide-Range DC Coil. Pick a coil with an integrated PWM economizer (e.g., ABB AF09-30-10-11) which maintains constant MMF from 100-250V. |
| Coil physically jams or air gap remains open | Reluctance is too high; MMF cannot generate sufficient flux. | Do not increase coil voltage. Clean the armature face or replace the mechanical assembly. Increasing MMF will just burn the new coil. |
Frequently Asked Questions
Can I measure magnetomotive force directly with a multimeter?
No. Your multimeter can only measure the electrical inputs (voltage and current) or the physical outputs (resistance). To find the MMF, you must measure the coil's resistance, calculate the operating current, and multiply that by the manufacturer's specified number of turns. You can measure the resulting flux density with a Gaussmeter, but MMF itself is a calculated value.
Why do DC contactor coils have built-in flyback diodes, but AC coils don't?
When you de-energize a DC coil, the collapsing magnetic field induces a massive reverse voltage spike (inductive kickback) that can destroy your PLC output transistors. A flyback diode provides a path for this current to dissipate. AC coils naturally cross zero and rely on the AC waveform's natural decay, often using RC snubber networks (resistor-capacitor) instead of diodes to manage the transient energy.
If I double the current through a coil, do I double the pulling force?
Not necessarily. While doubling the current doubles the MMF, the physical pulling force of an electromagnet is proportional to the square of the magnetic flux. However, if the steel core reaches magnetic saturation, doubling the current will yield almost zero increase in flux, meaning the pulling force plateaus while the coil simply overheats.
When replacing or designing inductive components, never guess the coil specifications based purely on physical size. Always verify the control voltage, calculate the expected MMF to ensure it clears the 80% pull-in threshold under worst-case voltage sag, and default to exact-match OEM part numbers like the Siemens 3RT2 series to guarantee the magnetic circuit behaves exactly as engineered.






