The Standard Electrical Wiring Size Chart (NEC Table 310.16)

This chart lists the allowable ampacity for copper conductors rated up to 2000 volts, with up to three current-carrying conductors in a raceway or cable, at an ambient temperature of 30°C (86°F). The columns represent the temperature rating of the wire insulation. Always cross-reference the insulation type printed on the wire jacket (e.g., THHN, THWN-2, NM-B) with these columns. According to the National Fire Protection Association (NFPA), this table is the baseline for all residential and commercial wire sizing before derating factors are applied.

Quick-Jump to Most Queried Sizes:

Source: NEC Table 310.16 (Copper Conductors, 30°C Ambient, Up to 3 Current-Carrying Conductors)
AWG Size60°C (140°F)75°C (167°F)90°C (194°F)
1415A20A25A
1220A25A30A
1030A35A40A
840A50A55A
655A65A75A
470A85A95A
385A100A115A
295A115A130A
1110A130A145A
1/0125A150A170A
2/0145A175A195A
3/0165A200A225A
4/0195A230A260A

Which Column Applies to Your Installation?

The most common mistake DIYers make is looking at the 90°C column because they bought THHN wire, then sizing their breaker to that higher number. NEC Article 110.14(C) dictates that your wire ampacity is ultimately limited by the temperature rating of the terminals the wire connects to, not just the wire insulation.

The Terminal Temperature Rule:
  • Circuits 100A or less (or using 14-1 AWG wire): Assume terminals are rated 60°C unless the equipment is explicitly stamped '75°C'. Most standard 15A and 20A receptacles fall here. Default to the 60°C column.
  • Circuits over 100A (or using 1/0 AWG and larger): Panelboard lugs and heavy-duty disconnects are universally rated 75°C. Use the 75°C column.
  • The 90°C Column: You only use this column to calculate derating adjustments (bundling and high ambient heat). The final derated ampacity must still be high enough to support the breaker size dictated by the 60°C or 75°C terminal limits.

Decision Path: Picking Your Exact Wire and Breaker

Use this decision tree to lock in your exact materials for standard residential branch circuits and feeders. This assumes standard copper wire and standard residential loads.

ScenarioMax Continuous LoadBreaker SizeConcrete Wire Pick (Copper)
Standard Bedroom/Living Room Outlet12A15A14 AWG NM-B (60°C rated)
Kitchen/Bath/Garage Small Appliance16A20A12 AWG NM-B (60°C rated)
Electric Dryer or RV Hookup24A30A10 AWG (NM-B or THHN)
Electric Range or Welder Receptacle40A50A6 AWG THHN/THWN-2
100A Subpanel Feeder (75°C Terminals)80A100A3 AWG THHN/THWN-2 or 1 AWG Aluminum

How Derating Modifies Your Base Ampacity

The chart above assumes perfect conditions: 30°C (86°F) ambient air and no more than three current-carrying conductors bundled together. Real-world jobsites rarely match this. When conditions change, you must apply derating multipliers to the 90°C column (even if your terminals are rated 60°C) to ensure the wire insulation doesn't melt inside the conduit.

1. Bundling Derating (NEC Table 310.15(C)(1))
If you pull 4 to 6 current-carrying conductors in a single conduit, multiply the 90°C base ampacity by 80%. (Note: Ground wires and neutrals in balanced 240V-only circuits do not count as current-carrying).

2. Ambient Temperature Derating (NEC Table 310.15(B)(1))
If your conduit runs through a 40°C (104°F) attic, multiply the 90°C base ampacity by 0.91.

Worked Example: You are pulling four 12 AWG THHN circuits (8 current-carrying conductors total) through a 40°C attic.
  • Base 90°C ampacity for 12 AWG = 30A.
  • Bundling derate (4-6 conductors per circuit pair, but let's assume 4-6 total in the pipe for this example) = 80%. (30A x 0.80 = 24A).
  • Temperature derate (40°C factor = 0.91). (24A x 0.91 = 21.8A).
  • Result: Your wire can safely carry 21.8A. Since NEC 240.4(D) strictly limits 12 AWG overcurrent protection to 20A max, you are clear to use a 20A breaker. If the math resulted in 18A, you would be forced to upsize to 10 AWG wire.

What This Chart Cannot Tell You

The electrical wiring size chart guarantees the wire won't overheat and start a fire under a specific load. It does not guarantee the equipment at the end of the wire will function correctly. For that, you must calculate voltage drop.

According to industry standards and resources like the Southwire voltage drop guidelines, a 3% maximum voltage drop is the accepted threshold for branch circuits, and 5% total for feeder plus branch combined. On a 120V circuit, 3% is 3.6V. If you run a 12 AWG wire 150 feet to a 15A space heater, the wire won't melt (it's well under the 20A limit), but the voltage at the heater will drop below 115V, causing poor performance and potential motor burnout. For long runs, use the formula VD = (2 x K x I x D) / CM (where K=12.9 for copper, I=load amps, D=one-way distance, CM=circular mils of the wire) and upsize the wire accordingly, regardless of the ampacity chart.

The Final Default Recommendation: Stop guessing terminal ratings. For all indoor staple-up branch circuits, buy 60°C rated NM-B (Romex) and use the 60°C column. For all conduit pulls, buy 90°C rated THHN/THWN-2 copper wire to give yourself maximum derating headroom, but terminate your 15A-50A breakers and receptacles using the 60°C ampacity limits. For any subpanel feeder over 100A, use the 75°C column and torque your lugs to the manufacturer's exact inch-pound spec.