For a standard 20A, 120V branch circuit under 50 feet, use 12 AWG THHN and 12 AWG bare copper wire for grounding on a 20A breaker. For runs exceeding 50 feet, upsize to 10 AWG current-carrying conductors and 10 AWG bare copper wire for grounding to maintain voltage drop limits.



SAFETY WARNING: Working inside electrical panels exposes you to lethal mains voltage. Always de-energize the panel, lock out the main breaker, and verify zero voltage with a tested multimeter or non-contact voltage tester before touching any conductors. Local codes may require a licensed electrician for panel work.

Baseline Assumptions and Ampacity Benchmarks

Before pulling any wire, we must define the physical and thermal environment. Wire sizing is not a guessing game; it is a strict calculation based on material, insulation, and ambient heat. The recommendations in this guide are built on the following baseline assumptions:

Baseline Assumptions Block:
Material: Copper (current-carrying and grounding)
Termination Temperature: 75°C column (standard for modern breakers and receptacles)
Ambient Temperature: 30°C (86°F) baseline, no extreme attic heat
Raceway: EMT (Electrical Metallic Tubing) conduit, maximum 3 current-carrying conductors

Under these conditions, we look to the Southwire Ampacity Chart (derived from NEC Table 310.16) to establish our baseline. While THHN insulation is rated for 90°C in the conduit body, we must size the wire based on the weakest link in the circuit—usually the 75°C or 60°C termination lugs on the breaker and receptacle.

Wire Size (AWG)Insulation Type90°C Column (Conduit)75°C Column (Terminations)NEC 240.4(D) Max Overcurrent
14 AWGTHHN / THWN-225A20A15A
12 AWGTHHN / THWN-230A25A20A
10 AWGTHHN / THWN-240A35A30A

Notice that while 12 AWG THHN can physically handle 25A at 75°C terminations, NEC Article 240.4(D) places a hard cap on small conductors. You cannot protect 12 AWG copper with anything larger than a 20A breaker, regardless of the 75°C column allowance.

Why This Size and Not One Smaller? The Physics of Fault Current

A common mistake among DIYers is assuming the bare copper wire for grounding (officially the Equipment Grounding Conductor, or EGC) only needs to handle minor leakage currents. Under normal operation, the EGC carries exactly zero amps. Its sole purpose is to act as a low-impedance highway for catastrophic fault current.

If a hot wire shorts to a metal tool casing, the circuit resistance drops to near zero. A dead short on a standard 120V residential circuit can instantly push 1,000A to 5,000A of current. The breaker’s magnetic trip mechanism requires roughly 10 to 15 milliseconds to physically snap open and clear this fault.

If you use a 14 AWG bare copper ground on a 20A breaker, the wire's higher resistance will limit the fault current. This delays the breaker's magnetic trip. Worse, the 14 AWG wire may act like a fuse and vaporize inside the conduit before the breaker clears, leaving the metal casing energized at 120V and creating a lethal shock hazard. NEC Table 250.122 dictates minimum EGC sizes specifically to ensure the wire survives the thermal and magnetic stress of the fault long enough for the breaker to trip.

The Voltage Drop Trap and Proportional Upsizing

Sizing the hot and neutral wires for ampacity is only half the battle. You must also check for voltage drop, which fundamentally alters your grounding wire size.

Let’s run a voltage drop check at a stated distance of 100 feet for our 20A, 120V circuit using 12 AWG copper. The resistance of 12 AWG copper is roughly 1.93 ohms per 1,000 feet.

Voltage Drop = (2 × Length × Current × Resistance) / 1000
Voltage Drop = (2 × 100 × 20 × 1.93) / 1000 = 7.72V

A 7.72V drop on a 120V circuit is a 6.4% drop. The NEC recommends a maximum 3% drop for branch circuits to ensure motors and electronics operate safely. To fix this, we must upsize the current-carrying conductors to 10 AWG (which drops the loss to roughly 4.0%, acceptable for many non-motor loads, or 8 AWG for a strict 3% target).

Here is where the National Fire Protection Association (NFPA) NEC rule 250.122(B) kicks in. If you upsize your ungrounded (hot) conductors to compensate for voltage drop, you must proportionally upsize your bare copper wire for grounding. You cannot run 10 AWG hots with a 12 AWG ground just because the breaker is still 20A. The ground must scale up in cross-sectional area alongside the hots to maintain the low-impedance fault path relative to the new wire size.

Decision Tree: Picking Your Exact Ground Wire AWG

Use this decision path to terminate your sizing debate and pick the exact part number for your next pull.

Circuit ScenarioBreaker SizeHot/Neutral AWG (Cu)Required Bare Copper Ground AWGConcrete Pick / Action
Standard run (< 50 ft), 120V or 240V20A12 AWG12 AWGBuy standard 12/2 NM-B or pull 12 AWG THHN + 12 AWG bare Cu.
Long run (50 - 100 ft), 120V20A10 AWG (upsized for V-drop)10 AWG (proportional upsize)Pull 10 AWG THHN hots + 10 AWG bare Cu ground.
Standard run (< 50 ft), 240V heavy appliance30A10 AWG10 AWGPull 10 AWG THHN hots + 10 AWG bare Cu ground.
Long run (50 - 80 ft), 240V EV Charger40A8 AWG (upsized for V-drop)8 AWG (proportional upsize)Pull 8 AWG THHN hots + 8 AWG bare Cu ground.
Bench Tip: When pulling individual THHN conductors in conduit, always buy a dedicated spool of bare copper for the EGC. While the NEC allows you to strip the insulation off a spare THHN wire to use as a ground in a pinch, doing so on long pulls ruins the wire's lubricity, increases conduit jamming risks, and wastes expensive insulated wire.

What Changes the Answer (and When the AHJ Steps In)

The sizing rules above apply to standard, single-run copper branch circuits. Several jobsite realities will force you to alter your calculations or call in professional engineering.

1. Bundling and Derating

If you pull more than three current-carrying conductors through a single conduit (e.g., two multi-wire branch circuits sharing a neutral), NEC Table 310.15(C)(1) requires you to derate the ampacity of the hot wires. If derating forces you to upsize the hot wires from 12 AWG to 10 AWG to maintain 20A capacity, NEC 250.122(B) once again mandates that you proportionally upsize the bare copper ground to 10 AWG. Note that the bare ground wire itself does not count as a current-carrying conductor for derating purposes.

2. Aluminum Current-Carrying Conductors

If you are feeding a subpanel using aluminum SER cable or THHN (e.g., 2-2-2-4 AL), your hot wires will be much larger than their copper equivalents due to aluminum's higher resistance and lower ampacity per AWG. However, NEC Table 250.122 bases the minimum ground size strictly on the breaker rating, not the hot wire material. A 100A breaker still requires an 8 AWG copper ground, even if the hots are 2 AWG aluminum. The interchangeability stops here: never use bare aluminum for an equipment ground in standard branch wiring, as it oxidizes and fails under fault conditions.

3. When an Engineer or AHJ Must Confirm

Do not rely on standard tables if your project crosses into these territories; your local Authority Having Jurisdiction (AHJ) or a licensed electrical engineer must sign off on the design:

  • Parallel Feeders: If you are running multiple conduit runs in parallel for a 400A+ service, NEC 250.122(C) requires a full-sized EGC in every parallel conduit, sized based on the overcurrent device, not divided among the pipes.
  • High Fault Current Services: In commercial settings with massive transformers, the available fault current can exceed the standard interrupting ratings. An engineer must perform a flash hazard and fault-current calculation to ensure the bare copper ground won't arc-flash and destroy the raceway.
  • Mixed Material Terminations: If your equipment specifies aluminum terminations but you are pulling copper, the AHJ must verify the use of anti-oxidant compounds and specific torque values.

For 95% of residential and light-commercial workshop builds, the decision tree above provides your final, code-compliant answer. Stick to the proportional upsizing rule, keep your terminations clean, and torque your grounding screws to the manufacturer's inch-pound specifications.