When sizing conductors for a branch circuit or feeder, guessing is not an option. The definitive reference for wire sizing in the United States is the NFPA 70 National Electrical Code (NEC), specifically Article 310.16. This standard dictates the maximum continuous current a wire can carry before its insulation begins to degrade. Below is the complete reference data you need to size your next run, followed by the critical rules for interpreting the temperature columns and applying derating factors.

The Core AWG Chart Amp Table (NEC 310.16)

How to read this table: Locate your wire gauge (AWG or kcmil) in the first column. Move right to the material (Copper or Aluminum). Finally, select the temperature column that matches the lowest rated termination in your circuit. Values are in Amperes (Amps). This data assumes an ambient temperature of 30°C (86°F) and not more than three current-carrying conductors in a raceway.

Bookmark Quick-Jumps: The most queried residential and light-commercial sizes are 14, 12, 10, 6, and 2 AWG. Note that per NEC 240.4(D), small conductors (14, 12, and 10 AWG copper) have strict overcurrent protection limits of 15A, 20A, and 30A respectively, regardless of the higher ampacities listed in the 75°C or 90°C columns.
NEC 310.16 Allowable Ampacities for Insulated Conductors (0-2000 Volts)
AWG Size Copper 60°C (140°F) Copper 75°C (167°F) Copper 90°C (194°F) Aluminum 75°C (167°F) Aluminum 90°C (194°F)
141520*25*
122025*30*
103035*40*
84050553040
65565754050
47085955565
3851001156575
2951151307590
1110130145100120
1/0125150170100120
2/0145175195115135
3/0165200225150180
4/0195230260180205

* Asterisk denotes ampacity exceeding the NEC 240.4(D) maximum overcurrent device rating for small copper conductors.

Which Temperature Column Applies to Your Installation?

The most common mistake DIYers and junior electricians make is looking at the wire jacket, seeing 'THHN 90°C', and immediately using the 90°C column to size the breaker. This violates the NEC 'weakest link' rule outlined in Article 110.14(C).

Your circuit's allowable ampacity is strictly limited by the lowest temperature rating of any connected component. This includes the breaker terminals, the receptacle lugs, splices, and the wire itself. Here is how to determine your column:

  • The 60°C Column: Use this for circuits rated 100 Amps or less if the termination temperature is unknown, or if you are connecting to older devices, specific smart switches, or NM-B (Romex) cable, which is universally rated for 60°C regardless of the individual wire insulation inside it.
  • The 75°C Column: This is the standard for modern residential and commercial installations. Most modern THWN/THHN wire, standard breakers, and commercial receptacles are rated for 75°C terminations. If your load is over 100A, you default to the 75°C column unless the equipment is specifically marked otherwise.
  • The 90°C Column: You almost never use this column to determine your final breaker size. The 90°C column is reserved almost exclusively as the starting baseline for derating calculations (explained below). Once the derating math is complete, the final adjusted ampacity must still be terminated according to the 60°C or 75°C limits.
Pro-Tip for Subpanels: When feeding a 100A subpanel, 4 AWG copper (85A at 75°C) is insufficient. You must step up to 3 AWG copper (100A at 75°C) or 1/0 aluminum. Do not use the 90°C column value of 95A for 4 AWG to justify a 100A breaker; the panel lugs will overheat.

How Derating Modifies Your Base Ampacity

The ampacities in the table above assume ideal conditions: an ambient temperature of 30°C (86°F) and a maximum of three current-carrying conductors bundled together. When you deviate from these conditions, the wires cannot dissipate heat as effectively, and you must apply adjustment factors found in NEC 310.15(C)(1) and 310.15(B)(1).

1. Bundling (More than 3 Current-Carrying Conductors):
If you pull four to six current-carrying conductors through a single conduit, you must multiply the base ampacity by 80%. For seven to nine conductors, the factor drops to 70%.

Worked Example: You are running a multi-wire circuit and have four current-carrying 12 AWG THHN wires in a conduit. You want to protect them with a 20A breaker.
- Base ampacity from the 90°C column for 12 AWG = 30A.
- Derating factor for 4 wires = 80% (0.80).
- Adjusted ampacity = 30A × 0.80 = 24A.
Since 24A is greater than the 20A breaker requirement (and greater than the 60°C termination limit of 20A), 12 AWG is perfectly legal here. However, if you had 10 wires in that conduit (50% derating), the math yields 15A. You would be forced to upsize to 10 AWG wire to maintain a 20A circuit.

2. Ambient Temperature Correction:
If your conduit runs through an attic in Arizona where ambient temperatures reach 50°C (122°F), you must apply a temperature correction factor. For 90°C wire at 50°C ambient, the multiplier is 0.82. You multiply the 90°C base ampacity by 0.82, and then ensure the result still satisfies your termination temperature requirements.

What This AWG Chart Cannot Tell You

While the standard ampacity charts provided by manufacturers like Cerro Wire and Southwire perfectly mirror the NEC for thermal limits, they do not account for the physical and electrical realities of long-distance power transmission. Always check these three factors before pulling wire:

  1. Voltage Drop: The NEC does not strictly enforce voltage drop for most branch circuits (it is a recommendation in Informational Note 310.15(B)), but a 3% maximum drop is the industry standard. If you are running a 20A circuit to a detached garage 150 feet away, 12 AWG wire will suffer a voltage drop exceeding 5%, causing motors to overheat and lights to dim. You must upsize to 8 AWG or 6 AWG purely to maintain voltage, even though 12 AWG handles the thermal ampacity.
  2. Physical Lug Capacity: A 4/0 AWG aluminum wire is rated for 180A at 75°C, making it technically sufficient for a 150A feeder. However, the physical lugs on a standard 150A residential main breaker often max out at 2/0 or 1/0 AWG. Always check the manufacturer's wiring diagram for the specific termination hardware before buying large-gauge wire.
  3. Short-Circuit Withstand Rating: Ampacity charts measure continuous thermal load. They do not tell you how the wire will react to a massive, instantaneous short-circuit current before the breaker trips. Proper breaker coordination and equipment interrupting ratings (AIC) are required to ensure the wire does not vaporize during a fault condition.