When sizing conductors for a residential or commercial branch circuit, guessing leads to tripped breakers, melted insulation, or failed inspections. The definitive reference for copper conductor ampacity in the United States is NEC Table 310.16 (formerly 310.15(B)(16)). This amp rating wire size chart gives you the exact allowable ampacities for copper conductors rated up to 2000 volts, assuming an ambient temperature of 30°C (86°F).

Below is the complete master chart, followed by a decision path to ensure you select the correct temperature column and apply the necessary derating factors for your specific installation.

The Master Amp Rating Wire Size Chart (NEC Table 310.16)

How to Read This Table: This table lists the base ampacity for copper conductors across three temperature columns: 60°C, 75°C, and 90°C. The 'Max Standard Breaker' column shows the next standard overcurrent protection device (OCPD) size per NEC 240.4(B), assuming no derating is required. Always verify the temperature rating of your termination points (breakers, lugs, receptacles) before choosing a column.
Source: NFPA 70 (National Electrical Code) Table 310.16 - Copper Conductors, 30°C Ambient
AWG / kcmil 60°C Column (NM-B / TW) 75°C Column (THWN / XHHW) 90°C Column (THHN / THWN-2) Max Standard Breaker (No Derating)
1415A20A25A15A (NEC 240.4(D) limits)
1220A25A30A20A (NEC 240.4(D) limits)
1030A35A40A30A (NEC 240.4(D) limits)
840A50A55A50A
655A65A75A60A
470A85A95A80A
385A100A115A100A
295A115A130A125A
1110A130A145A125A
1/0125A150A170A150A
2/0145A175A195A175A
3/0165A200A225A200A
4/0195A230A260A225A

Quick-Jump: Most Queried Wire and Breaker Sizes

For standard residential branch circuits, bookmark these baseline pairings. These assume standard NM-B (Romex) cable in a typical wall cavity with no more than three current-carrying conductors bundled together.

  • 15-Amp Breaker (Lighting/General Purpose): 14 AWG Copper (Minimum). 12 AWG recommended for future-proofing.
  • 20-Amp Breaker (Kitchen/Bath/Outlets): 12 AWG Copper (Strict minimum).
  • 30-Amp Breaker (Dryer/HVAC Condenser): 10 AWG Copper.
  • 40-Amp Breaker (Range/Cooktop): 8 AWG Copper.
  • 50-Amp Breaker (EV Charger/Hot Tub): 6 AWG Copper.

Decision Path: Which Temperature Column Applies to You?

A common mistake is using the 90°C column for THHN wire simply because the wire jacket is rated for 90°C. The National Electrical Code (NEC) requires that the ampacity of a conductor cannot exceed the lowest temperature rating of any connected device, terminal, or splice. Use this decision tree to find your governing column.

IF Your Installation Is... THEN Use This Column... Why?
Using NM-B (Romex) cable for any branch circuit. 60°C Column NEC 334.80 mandates NM-B ampacity is determined by the 60°C column, regardless of the 90°C rating of the internal conductors.
Using THHN/THWN-2 in conduit, terminating on a breaker or receptacle rated 15A to 100A. 60°C Column NEC 110.14(C)(1)(a) requires terminations for equipment rated 100A or less to be sized using the 60°C column unless the equipment is specifically marked for 75°C.
Using THHN/THWN-2 in conduit, terminating on a panel lug or breaker rated over 100A. 75°C Column NEC 110.14(C)(1)(b) allows the 75°C column for equipment rated over 100A, as modern panel lugs are universally rated for 75°C.
Calculating voltage drop or applying derating factors before termination. 90°C Column The 90°C column is used as the starting baseline for math (derating and voltage drop), but the final adjusted ampacity cannot exceed the 60°C or 75°C termination limits.

Derating: When Your Base Ampacity Drops

The amp rating wire size chart above assumes ideal conditions: an ambient temperature of 30°C (86°F) and no more than three current-carrying conductors (CCCs) in a single raceway or cable. When reality deviates from this, you must derate the 90°C column baseline.

1. Bundling (More than 3 CCCs)

When you pull multiple circuits through a single conduit, the heat generated by adjacent wires cannot dissipate. Per NEC Table 310.15(C)(1), if you have 4 to 6 CCCs in a conduit, you must multiply the 90°C base ampacity by 80%. For 7 to 9 CCCs, multiply by 70%.

Worked Example: You are pulling three 20A circuits (6 CCCs total) through a single EMT conduit using 12 AWG THHN.
• Base 90°C ampacity for 12 AWG = 30A.
• Derating factor for 6 CCCs = 80%.
• Adjusted ampacity = 30A × 0.80 = 24A.
• Because 24A exceeds the 20A breaker, 12 AWG is legally permissible here. However, if you added a fourth circuit (8 CCCs, 70% derating), the adjusted ampacity drops to 21A. You would be forced to upsize to 10 AWG THHN to maintain a safe margin.

2. High Ambient Temperature

If your conduit runs through an attic in a southern climate where temperatures regularly exceed 86°F (30°C), you must apply the temperature correction factors in NEC Table 310.15(B)(1). At 122°F (50°C), the correction factor for 90°C insulation is 0.82. Always multiply the bundling factor and the temperature factor together if both conditions exist.

What This Chart Cannot Tell You (And Your Default Pick)

The NEC ampacity tables dictate the maximum current a wire can carry before its insulation degrades or becomes a fire hazard. They do not account for voltage drop. According to the Copper Development Association, a voltage drop exceeding 3% on a branch circuit can cause motors to overheat, LED drivers to flicker, and electronics to brown out.

For example, a 50-amp EV charger located 120 feet from the panel using 6 AWG copper will experience a voltage drop of roughly 4.1% at full load. The 6 AWG wire will not melt (it satisfies the ampacity chart), but the performance will suffer. To fix this, you must upsize to 4 AWG copper to bring the drop back under 3%.

The Concrete Default Rule: Stop second-guessing your installation. For any standard residential branch circuit under 100 amps running under 50 feet, select the copper wire size from the 60°C column that exactly matches or exceeds your breaker size. If your run exceeds 50 feet, upsize the wire by one AWG to neutralize voltage drop, but terminate it based on the 60°C or 75°C ampacity limits of your breaker. If you are pulling more than three current-carrying conductors in a conduit, switch to THHN, start your math at the 90°C column, apply the 80% derating multiplier, and verify the final number still exceeds your breaker rating.