The ampacity of 2 AWG wire depends entirely on the conductor material (copper vs. aluminum) and the insulation temperature rating. For standard residential and commercial installations, 2 AWG copper wire has an ampacity of 115 amps (at 75°C) or 95 amps (at 60°C). 2 AWG aluminum wire is rated for 90 amps (at 75°C) or 75 amps (at 60°C). If you are using 90°C rated insulation like THHN in a raceway where terminals are also rated for 90°C—which is rare in standard panels—copper jumps to 130A and aluminum to 100A.

Below is the complete reference data, the rules for selecting the correct temperature column, and the real-world derating math that dictates what this wire can actually handle on your jobsite.

The Master 2 AWG Ampacity Reference Table

How to read this table: The rows represent the conductor material. The columns represent the temperature rating of the wire insulation and the connected terminals. The values are in Amperes (A). This data is sourced directly from NFPA 70 (NEC) Table 310.16, based on an ambient temperature of 30°C (86°F) and not more than three current-carrying conductors in a raceway.

Table 310.16 Ampacities for Insulated Conductors (Sizes 4 AWG to 1/0 AWG)
AWG Size Material 60°C Column (TW, UF) 75°C Column (THHW, THW, XHHW) 90°C Column (THHN, THWN-2)
4 AWG Copper 70A 85A 95A
4 AWG Aluminum 55A 65A 75A
3 AWG Copper 85A 100A 115A
3 AWG Aluminum 65A 75A 85A
2 AWG Copper 95A 115A 130A
2 AWG Aluminum 75A 90A 100A
1 AWG Copper 110A 130A 145A
1 AWG Aluminum 85A 100A 115A
1/0 AWG Copper 125A 150A 170A
1/0 AWG Aluminum 100A 120A 135A
Bookmark Tip: If you are pulling standard THHN/THWN-2 wire from a spool, look at the 90°C column for derating calculations, but use the 75°C column for your final breaker sizing. Most residential and commercial lugs are only rated to 75°C.

Which Temperature Column Applies to Your Installation?

A common mistake on the bench and in the panel is looking at the 90°C stamp on a spool of THHN wire and assuming you can use the 90°C ampacity column. Under NEC 110.14(C), the allowable ampacity of a circuit is limited by the lowest temperature rating of any connected component, including breaker terminals, busbars, and lugs.

  • The 60°C Column: Use this for older installations, NM-B (Romex) cable assemblies, or when connecting to equipment explicitly marked for 60°C. Note that while NM-B wire contains 90°C rated conductors, NEC 334.80 mandates that its ampacity be determined using the 60°C column.
  • The 75°C Column: This is your default for almost all modern THW, THHW, and XHHW wire, and for terminating THHN wire into standard commercial and residential breakers (which are typically rated 75°C). For 2 AWG copper, this locks your base ampacity at 115A.
  • The 90°C Column: Use this only as the starting baseline for derating calculations (ambient temperature and bundling). You can only use the 90°C final ampacity if every single termination point in the circuit is explicitly rated and marked for 90°C, which is exceptionally rare in standard building wiring.

Derating Factors: What the Base Table Cannot Tell You

The table above assumes a perfect environment: an ambient temperature of 30°C (86°F) and a maximum of three current-carrying conductors in a single raceway. When real-world conditions deviate, NEC 310.15 requires you to apply correction factors that can drastically reduce the 2 AWG ampacity.

Ambient Temperature Corrections

If your conduit runs through a hot attic or near a boiler, the wire's ability to shed heat drops. For example, if your 2 AWG THHN copper wire runs through an attic that reaches 40°C (104°F), you must apply a 0.91 correction factor to the 90°C base ampacity (130A × 0.91 = 118.3A). Since 118.3A is still above the 75°C terminal limit (115A), your final ampacity remains 115A.

Bundling (More Than 3 Current-Carrying Conductors)

When you pull multiple circuits through the same conduit, the wires heat each other up. If you pull four 2 AWG THHN copper conductors (e.g., two multi-wire branch circuits or a 3-phase feeder with a neutral that carries unbalanced current), you must apply an 80% adjustment factor.

Real-World Derating Example:
Imagine four 2 AWG THHN copper conductors in a conduit running through a 40°C (104°F) attic.

  1. Start with 90°C base ampacity: 130A
  2. Apply 40°C temperature correction (0.91): 130A × 0.91 = 118.3A
  3. Apply bundling adjustment for 4 conductors (0.80): 118.3A × 0.80 = 94.64A

Because the derated ampacity (94.64A) is now lower than the 75°C terminal rating (115A), the 94.64A value governs. You must drop down to a standard 90A breaker. The base table cannot tell you this; you must run the math for your specific installation.

2 AWG Ampacity Frequently Asked Questions

What size breaker can I use with 2 AWG copper wire?

Under the 75°C column, 2 AWG copper has an ampacity of 115A. Because 115A is not a standard overcurrent device size listed in NEC 240.6, NEC 240.4(B) permits you to round up to the next standard size, which is 125 amps. However, this only applies if the load is non-continuous (operating for less than 3 hours). If you are feeding a continuous load (like a commercial HVAC unit or EV charger), you must size the conductor at 125% of the continuous load, meaning a 125A breaker would require a continuous load of no more than 100A.

Can I use 2 AWG aluminum wire for a 100-amp subpanel feeder?

No. 2 AWG aluminum wire has a 75°C ampacity of 90 amps. You cannot protect a 90A conductor with a 100A breaker, as 90A is a standard breaker size (meaning the 'next size up' rule does not apply). To feed a 100-amp subpanel using aluminum, you must step up to 1/0 AWG aluminum (rated 120A at 75°C) or, at the absolute minimum, 1 AWG aluminum (rated exactly 100A at 75°C, though 1/0 is heavily preferred for voltage drop and mechanical strength at termination lugs).

How far can I run 2 AWG wire before voltage drop limits the ampacity?

Voltage drop does not change the thermal ampacity defined by the NEC, but it dictates the practical current you can push over a distance. For a 240V circuit running at the full 115A copper ampacity, a standard 3% allowable voltage drop equates to 7.2 volts. Using the single-phase voltage drop formula (Distance = [Circular Mils × Voltage Drop] / [2 × K × Current]), where 2 AWG copper has 66,360 circular mils and K=12.9:

Distance = (66,360 × 7.2) / (2 × 12.9 × 115) = 161 feet.

If your 2 AWG copper run exceeds 160 feet at full load, you will exceed a 3% voltage drop. To maintain both ampacity and voltage integrity over longer runs, you must upsize to 1 AWG or 1/0 AWG copper.